Tab

le 2b.

Electrical Data - P

ac

ka

g

ed A/C - P6 Units - 3 Phase

, 60 Her

tz

Model Number

Allowable V

oltage Range

Compressors

Outdoor motors (2) ea.

Indoor Motor

Mult.

Cir

c.

“A”

Single Cir

cuit

- P6SP

& H5HK kit

MCA

MOP

MCA

MOP

Factor

y Drive Data:

P6SP

Min

Max

Qty

RLA

LRA

FLA

FLA

No Heater Kit

9 kW

18 kW

30 kW

35 kW

9 kW

18 kW

30 kW

35 kW

-072 C

187

253

1 ea.

19

123

1.5

3.2 - 3.1

30 - 30

45 - 45

30 - 31

50 - 57

80 - 91

- n/a -

45 - 45

55 - 60

90 - 100

- n/a -

-072 D

414

506

1 ea.

9.7

62

0.8

1.5

16

20

17

29

46

- n/a -

20

30

50

- n/a -

-090 C

187

253

2 ea.

13.1

83.1

2.3

6.2 - 5.8

41 - 40

50 - 50

41 - 40

54 - 60

83 - 94

99 - 1

12

50 - 50

55 - 70

90 - 100

100 - 125

-090 D

414

506

2 ea.

6.1

41

1.2

2.9

19

25

19

31

47

56

25

35

50

60

-120 C

187

253

2 ea.

16.0

11

0

2.3

6.2 - 5.8

47 - 47

60 - 60

47 - 47

54 - 60

83 - 94

99 - 1

12

60 - 60

60 - 70

90 - 100

100 - 125

-120 D

414

506

2 ea.

7.8

52

1.2

2.9

23

30

23

31

47

56

30

35

50

60

Medium Static Drive Data:

-072 C

187

253

1 ea.

19

123

1.5

4.4 - 4.2

32 - 31

50 - 45

32 - 33

51 - 58

81 - 92

- n/a -

50 - 45

60 - 60

90 - 100

- n/a -

-072 D

414

506

1 ea.

9.7

62

0.8

2.1

16

25

18

30

46

- n/a -

25

35

50

- n/a -

-090 C

187

253

2 ea.

13.1

83.1

2.3

9.1 - 8.9

44 - 43

55 - 55

44 - 43

57 - 64

87 - 98

103 - 1

16

55 - 55

60 - 70

90 - 100

100 - 125

-090 D

414

506

2 ea.

6.1

41

1.2

4.4

21

25

21

33

49

58

25

35

50

60

-120 C

Not Applicable

-120 D

High Static Drive Data:

-072 C

Not Applicable

-072 D

-090 C

187

253

2 ea.

13.1

83.1

2.3

9.1 - 8.9

44 - 43

55 - 55

44 - 43

57 - 64

87 - 98

103 - 1

16

55 - 55

60 - 70

90 - 100

100 - 125

-090 D

414

506

2 ea.

6.1

41

1.2

4.4

21

25

21

33

49

58

25

35

50

60

-120 C

187

253

2 ea.

16.0

11

0

2.3

9.1 - 8.9

50 - 50

60 - 60

50 - 50

57 - 64

87 - 98

103 - 1

16

60 - 60

60 - 70

90 - 100

100 - 125

-120 D

414

506

2 ea.

7.8

52

1.2

4.4

25

30

25

33

49

58

30

35

50

60

Notes:

FLA

= Full Load

Amps

RLA

= Rated Load

Amps

LRA

= Locked Rotor

Amps

MCA

= Minimum Circuit

Ampacity

MOP

= Maximum Over-Current Protection

C Series, Electrical unit data shown for 208V - 230V D Series, Electrical unit data shown for 460V

When used with 917468 Dual Circuit

Adapter Kit - See

Table 2 for Multiple Circuit “B” data

This manual is related to the following products: