Reznor Q6SP Option - Installation - Elec Heating User Manual
Page 9

9
Tab
le 2b.
Electrical Data - P
ac
ka
g
ed A/C - P6 Units - 3 Phase
, 60 Her
tz
Model Number
Allowable V
oltage Range
Compressors
Outdoor motors (2) ea.
Indoor Motor
Mult.
Cir
c.
“A”
†
Single Cir
cuit
- P6SP
& H5HK kit
MCA
MOP
MCA
MOP
Factor
y Drive Data:
P6SP
Min
Max
Qty
RLA
LRA
FLA
FLA
No Heater Kit
9 kW
18 kW
30 kW
35 kW
9 kW
18 kW
30 kW
35 kW
-072 C
187
253
1 ea.
19
123
1.5
3.2 - 3.1
30 - 30
45 - 45
30 - 31
50 - 57
80 - 91
- n/a -
45 - 45
55 - 60
90 - 100
- n/a -
-072 D
414
506
1 ea.
9.7
62
0.8
1.5
16
20
17
29
46
- n/a -
20
30
50
- n/a -
-090 C
187
253
2 ea.
13.1
83.1
2.3
6.2 - 5.8
41 - 40
50 - 50
41 - 40
54 - 60
83 - 94
99 - 1
12
50 - 50
55 - 70
90 - 100
100 - 125
-090 D
414
506
2 ea.
6.1
41
1.2
2.9
19
25
19
31
47
56
25
35
50
60
-120 C
187
253
2 ea.
16.0
11
0
2.3
6.2 - 5.8
47 - 47
60 - 60
47 - 47
54 - 60
83 - 94
99 - 1
12
60 - 60
60 - 70
90 - 100
100 - 125
-120 D
414
506
2 ea.
7.8
52
1.2
2.9
23
30
23
31
47
56
30
35
50
60
Medium Static Drive Data:
-072 C
187
253
1 ea.
19
123
1.5
4.4 - 4.2
32 - 31
50 - 45
32 - 33
51 - 58
81 - 92
- n/a -
50 - 45
60 - 60
90 - 100
- n/a -
-072 D
414
506
1 ea.
9.7
62
0.8
2.1
16
25
18
30
46
- n/a -
25
35
50
- n/a -
-090 C
187
253
2 ea.
13.1
83.1
2.3
9.1 - 8.9
44 - 43
55 - 55
44 - 43
57 - 64
87 - 98
103 - 1
16
55 - 55
60 - 70
90 - 100
100 - 125
-090 D
414
506
2 ea.
6.1
41
1.2
4.4
21
25
21
33
49
58
25
35
50
60
-120 C
Not Applicable
-120 D
High Static Drive Data:
-072 C
Not Applicable
-072 D
-090 C
187
253
2 ea.
13.1
83.1
2.3
9.1 - 8.9
44 - 43
55 - 55
44 - 43
57 - 64
87 - 98
103 - 1
16
55 - 55
60 - 70
90 - 100
100 - 125
-090 D
414
506
2 ea.
6.1
41
1.2
4.4
21
25
21
33
49
58
25
35
50
60
-120 C
187
253
2 ea.
16.0
11
0
2.3
9.1 - 8.9
50 - 50
60 - 60
50 - 50
57 - 64
87 - 98
103 - 1
16
60 - 60
60 - 70
90 - 100
100 - 125
-120 D
414
506
2 ea.
7.8
52
1.2
4.4
25
30
25
33
49
58
30
35
50
60
Notes:
FLA
= Full Load
Amps
RLA
= Rated Load
Amps
LRA
= Locked Rotor
Amps
MCA
= Minimum Circuit
Ampacity
MOP
= Maximum Over-Current Protection
C Series, Electrical unit data shown for 208V - 230V D Series, Electrical unit data shown for 460V
†
When used with 917468 Dual Circuit
Adapter Kit - See
Table 2 for Multiple Circuit “B” data