Warning – Reznor Q6SP Option - Installation - Elec Heating User Manual
Page 5

5
WARNING:
Heaters may not function properly if 
elements are not installed per these 
instructions.
IMPORTANT: Application of H5HK-035Q
and H5HK-035S Electric Heat Kits.
The three (3)- 160 Deg. F High Temperature
limits installed on the element assembly 
must be replaced with the three (3)- 210 Deg. 
F High Temperature limits supplied with the 
electric heat kit on all 7.5 Ton package Air 
Conditioners and 7.5 & 10 Ton Q5,Q6 & P6 
Package units. Ensure all wiring and con-
nections are to unit wiring diagram when 
complete. Short cycling of equipment will 
occur if proper limits are not installed. (See 
table 1 for proper limit application).
Remove Element/Field Wiring Access panel.
*P4S(M,N) Series – Determine the number of 
element close-off plates to be removed from 
mounting panel based on size of kit being in-
stalled. Set screws aside for later use and discard 
close-off plates.
P6SP/Q6SP/Q5SN Series – Remove the ele-
ment opening cover. Four (4) mounting plates 
are required around the element kit to secure 
and seal the opening. Mount the longer plates 
to the top and bottom of the element assembly 
prior to inserting into the unit. Secure the element 
assembly in place using screws removed with 
the cover. Attach the remaining two side close 
off plates.
NOTE: 240V -009Q and -018Q kits
require the addition of a blank element plate 
included in the kit. See Figure 1B.
WARNING:
Install heater elements starting 
closest to the blower with high 
temperature limits located at the 
top of the assembly. See Figure 1A. 
Be careful not to damage heater 
element wires or ceramic element 
supports while inserting through 
panel opening. Ensure heater 
element support rods slide into the 
alignment holes in the back of the 
element housing box. Secure the 
element assembly to the mounting 
panel with the screws removed 
when removing the element close-
off plates.
CONTROL MOUNTING
Electric Heater Kits without Circuit Breakers
 
Three pole control contactors locate on the ele-
ment mounting panel above the factory installed 
terminal block. See Figure 2 for location of the 
two (2) mounting holes required for kit power 
wiring to be of proper length. Mount contactor 
with screws provided in kit.
Electric Heater Kits with Circuit Breakers
NOTE: Circuit Breakers supplied with the 
H5HK electric heater kits are for short circuit-
protection of the heater element internal 
wiring and DO NOT serve as a disconnect. 
Circuit Breakers supplied with the H5HK heater 
kits 
DO NOT provide over-current protection of
the supply wiring. Over-current protection of the 
supply wiring must be provided at the distribution 
panel and sized as shown on the unit rating label 
or in Table 2 of these instructions.
Contactor/Circuit Breaker control panel is 
shipped fully assembled for mounting above 
the factory installed terminal block using the six 
(6) mounting holes provided. See Figure 2 for 
layout location and mount panel with screws 
provided in kit.
Figure 1B. Mounting Plates