Warning – Reznor Q6SP Option - Installation - Elec Heating User Manual

Page 5

background image

5

WARNING:

Heaters may not function properly if
elements are not installed per these
instructions.

IMPORTANT: Application of H5HK-035Q
and H5HK-035S Electric Heat Kits.

The three (3)- 160 Deg. F High Temperature
limits installed on the element assembly
must be replaced with the three (3)- 210 Deg.
F High Temperature limits supplied with the
electric heat kit on all 7.5 Ton package Air
Conditioners and 7.5 & 10 Ton Q5,Q6 & P6
Package units. Ensure all wiring and con-
nections are to unit wiring diagram when
complete. Short cycling of equipment will
occur if proper limits are not installed. (See
table 1 for proper limit application).

Remove Element/Field Wiring Access panel.

*P4S(M,N) Series – Determine the number of
element close-off plates to be removed from
mounting panel based on size of kit being in-
stalled. Set screws aside for later use and discard
close-off plates.

P6SP/Q6SP/Q5SN Series – Remove the ele-
ment opening cover. Four (4) mounting plates
are required around the element kit to secure
and seal the opening. Mount the longer plates
to the top and bottom of the element assembly
prior to inserting into the unit. Secure the element
assembly in place using screws removed with
the cover. Attach the remaining two side close

off plates.

NOTE: 240V -009Q and -018Q kits

require the addition of a blank element plate
included in the kit. See Figure 1B.

WARNING:

Install heater elements starting
closest to the blower with high
temperature limits located at the
top of the assembly. See Figure 1A.
Be careful not to damage heater
element wires or ceramic element
supports while inserting through
panel opening. Ensure heater
element support rods slide into the
alignment holes in the back of the
element housing box. Secure the
element assembly to the mounting
panel with the screws removed
when removing the element close-
off plates.

CONTROL MOUNTING

Electric Heater Kits without Circuit Breakers


Three pole control contactors locate on the ele-
ment mounting panel above the factory installed
terminal block. See Figure 2 for location of the
two (2) mounting holes required for kit power
wiring to be of proper length. Mount contactor
with screws provided in kit.

Electric Heater Kits with Circuit Breakers

NOTE: Circuit Breakers supplied with the
H5HK electric heater kits are for short circuit-
protection of the heater element internal
wiring and DO NOT serve as a disconnect.
Circuit Breakers supplied with the H5HK heater
kits

DO NOT provide over-current protection of

the supply wiring. Over-current protection of the
supply wiring must be provided at the distribution
panel and sized as shown on the unit rating label
or in Table 2 of these instructions.

Contactor/Circuit Breaker control panel is
shipped fully assembled for mounting above
the factory installed terminal block using the six
(6) mounting holes provided. See Figure 2 for
layout location and mount panel with screws
provided in kit.

Figure 1B. Mounting Plates