Excerpts from NEC 2005 handbook - based on NFPA 70

Partial Table 310.16 Allowable Ampacities of Insulated Conductors (0-2000 Volts)

- Not more then 3 current carrying conductors in cable or raceway
- Based on Ambient Temp of 30˚C

Copper Wire Only

Size

Temperature Rating of Conductor

Size

AWG

or

kcmil

60

˚C

75

˚C

90

˚C

AWG

or

kcmil

14

20

20

25

14

How to Estimate Unit Supply Wire Requirements:

12

25

25

30

12

10

30

35

40

10

1) Determine Nominal Input Voltage

8

40

50

55

8

2) Estimate Length of Wire from Breaker to Unit Disconnect

6

55

65

75

6

3) Find Unit MCA for desired configuration

4

70

85

95

4

4) Using the minimum wire size based on the unit MCA, calculate the %

Voltage Drop to determine the initial wire gauge

3

85

100

110

3

2

95

115

130

2

The %VD should be 3% or less at the unit

1

110

130

150

1

5) Verify Unit Voltage is within the Appliances min/max limits

1/0

125

150

170

1/0

6) Verify that the Wire ampacity (corrected for temperature & the # of

conductors) is above the Appliances MCA

2/0

145

175

195

2/0

3/0

165

200

225

3/0

7) Based on final wire gauge selection, determine conduit size. Refer to

NEC for details and allowable fill rate

Amb. Temperature Correction Factors

Amb.

Temp

(

˚C)

Temperature Rating of Conductor

Amb.

Temp

(

˚F)

60

˚C

75

˚C

90

˚C

8) Based on Appliance MOP and final wire selection, make selection of

Appliance branch circuit protection

21-25

1.08

1.05

1.04

70-77

26-30

1.00

1.00

1.00

78-86

31-35

0.91

0.94

0.96

87-95

36-40

0.82

0.88

0.91

96-104

41-45

0.71

0.82

0.87

105-113

46-50

0.58

0.75

0.82

114-122

51-55

0.41

0.67

0.76

123-131

Partial Table 310.15(B)(2)(a) Adjustment factors for more than three current-carrying

conductors in a raceway or cable

# of Current-Carrying Con-

ductors

Amount to adjust values in Table

310.16 after correction for Ambient

Temperature (if necessary)

4 to 6

80%

7 to 9

70%

Partial Table 9 Effective Impedance for 600V Cables, 3Ø, 60 Hz, 75˚C - 3 single current-carrying conductors in conduit

Uncoated Copper Wire Only

Effective Impedance (Z) at 0.85 PF

Ω

to Neutral / 1000 ft

AWG

or

kcmil

PVC

Conduit

Aluminum

Conduit

Steel

Conduit

14

2.7

2.7

2.7

12

1.7

1.7

1.7

10

1.1

1.1

1.1

8

0.69

0.69

0.70

6

0.44

0.45

0.45

4

0.29

0.29

0.30

3

0.23

0.24

0.24

2

0.19

0.19

0.20

1

0.16

0.16

0.16

1/0

0.13

0.13

0.13

2/0

0.11

0.11

0.11

3/0

0.088

0.092

0.094

The above tables and recommended procedures are provided for reference only, for complete details refer to the current

version of the National Electric Code, the applicable local codes & ordinances, or consult a qualified professional.

100

%

3

1000

9

Ч

=

Ч

=

Ч

Ч

=

tage

NomLineVol

p

VoltageDro

p

VoltageDro

p

VoltageDro

p

VoltageDro

UnitMCA

ft

gth

CircuitLen

Value

Table

p

VoltageDro

Line

to

Line

Neutraul

to

Line

Line

to

Line

Neutraul

to

Line