Reznor Q6SP Option - Installation - Elec Heating User Manual

Page 11

background image

11

Tab

le 2d.

Electrical Data - P

ac

ka

g

ed H/P - Q6 Units - 3 Phase

, 60 Her

tz

Model

Number

Allo

w

ab

le

V

oltage

Range

Compressors

Outdoor

motors

(2) ea.

Indoor

Motor

Mult.

Cir

c.

“A”

Single Cir

cuit

- Q6SP & H5HK kit

MCA

MOP

MCA

MOP

Factor

y Drive Data:

Q6SP

Min

Max

Qty

RLA

LRA

FLA

FLA

No Heater Kit

9 kW

18 kW

30 kW

35 kW

9 kW

18 kW

30 kW

35 kW

-090 C

187

253

2 ea.

13.1

83.1

2.3

4.2 - 4.0

39 - 39

50 - 50

49 - 52

71 - 78

101 - 112

116 - 130

55 - 55

80 - 80

110 - 125

125 - 150

-090 D

414

506

2 ea.

6.1

41

1.2

2.0

19

20

27

40

56

65

30

45

60

70

-120 C

187

253

2 ea.

15.6

110

2.3

6.2 - 5.8

46 - 46

60 - 60

54 - 57

76 - 83

106 - 117

121 - 135

60 - 60

80 - 90

110 - 125

125 - 150

-120 D

414

506

2 ea.

7.8

52

1.2

2.9

23

30

30

43

59

68

35

45

60

70

High Static Drive Data:

-090 C

187

253

2 ea.

13.1

83.1

2.3

9.1 - 8.9

44 - 44

55 - 55

54 - 57

76 - 83

106 - 117

121 - 135

60 - 60

80 - 90

110 - 125

125 - 150

-090 D

414

506

2 ea.

6.1

41

1.2

4.4

21

25

30

42

58

67

35

45

60

70

-120 C

187

253

2 ea.

16.0

110

2.3

9.1 - 8.9

49 - 49

60 - 60

57 - 61

79 - 86

109 - 120

124 - 138

60 - 70

80 - 90

110 - 125

125 - 150

-120 D

414

506

2 ea.

7.8

52

1.2

4.4

25

30

32

44

60

69

35

45

70

70

Tab

le 2d.

Electrical Data - P

ac

ka

g

ed H/P - Q6 Units - 3 Phase

, 60 Her

tz

FLA = Full Load Amps

Notes:

MCA = Minim

um Circuit Ampacity

C Ser

ies

, Electr

ical unit data sho

wn f

or 208V - 230V

RLA = Rated Load Amps

MOP = Maxim

um Ov

er-Current Protection

D Ser

ies

, Electr

ical unit data sho

wn f

or 460V

LRA = Loc

ked Rotor Amps

When used with 917468 Dual Circuit Adapter Kit - See

Tab

le 2 f

or Multiple Circuit

“B”

data