Clearance – Reznor Q6SP Option - Installation - Elec Heating User Manual
Page 7

7
Heater Kit Electrical Data @ Rated Voltage
3 Phase, 60 Hertz
Multiple Circuit “B” †
Minimum
Circuit
Ampacity
Maximum
Over-Current
Rating
Rated
Volts
Model
Number
Line
Amps
Heater
Watts
208V
H5HK-009Q
18.8
6,760
24
25
H5HK-018Q
36.3
13,069
46
50
H5HK-030Q
60.0
21,632
76
80
H5HK-035Q
72.6
26,139
91
100
240V
H5HK-009Q
21.7
9,000
28
30
H5HK-018Q
41.9
17,400
53
55
H5HK-030Q
69.3
28,800
87
90
H5HK-035Q
83.7
34,800
105
110
480V
H5HK-009S
11.9
9,900
15
20
H5HK-018S
21.7
18,000
28
30
H5HK-030S
34.6
28,800
44
45
H5HK-035S
41.9
34,800
53
55
† When used with 917468 kit, See applicable unit chart for Multiple Circuit “A” data
‡
Refer to Table 1 for allowable unit / H5HK combinations
CLEARANCE
All H5HK Electric Heater kits are approved
for use in installations with zero-clearance to
combustibles at any blower speed allowed on
the units blower performance charts for both
Horizontal and Downflow applications when
installed according to these instructions and
other instructions included with the unit and
other approved accessories. (See warning for
downflow applications in Element Installation
section, page 5)
Table 2. Electrical Data - H5HK Series Heater Kits