beautypg.com

Grounding, Blower speed, Thermostat connections – Reznor Q6SE Unit Installation Manual User Manual

Page 9: Grounding blower speed thermostat connections, Warning, Caution

background image

9

and minimum size of electrical conductors and circuit

protection must be in compliance with information listed

on the outdoor unit data label. Any other wiring methods

must be acceptable to authority having jurisdiction.

• The outdoor unit requires both power and control circuit

electrical connections. Refer to

Figure 8 (page 15)

for identification and location of outdoor unit field wiring

interfaces. Make all electrical connections in accordance

with all applicable codes and ordinances.

• Overcurrent protection must be provided at the branch

circuit distribution panel and sized as shown on the unit

rating label and according to applicable local codes.

See the unit rating plate for minimum circuit ampacity

and maximum overcurrent protection limits.

• Provide power supply for the unit in accordance with the

unit wiring diagram, and the unit rating plate. Connect

the line-voltage leads to the terminals on the contactor

inside the control compartment.

• Use only copper wire for the line voltage power supply

to this unit as listed in

Table 1

. Use proper code agency

listed conduit and a conduit connector for connecting

the supply wires to the unit. Use of rain tight conduit is

recommended.

• Units are shipped from the factory wired for 240 volt

operation. Remove the lead from the transformer terminal

marked 240V and connect it to the terminal marked

208V.

• Optional equipment requiring connection to the power

or control circuits must be wired in strict accordance of

the NEC (ANSI/NFPA 70), applicable local codes, and

the instructions provided with the equipment.

coPPER WIRE SIZE — AWG

(1% VoltAGE DRoP)

SUPPlY WIRE lEnGtH-FEEt

SUPPlY cIRcUIt

AMPAcItY

200

150

100

50

6

8

10

14

15

4

6

8

12

20

4

6

8

10

25

4

4

6

10

30

3

4

6

8

35

3

4

6

8

40

2

3

4

6

45

2

3

4

6

50

2

3

4

6

55

1

2

3

4

60

Wire Size based on N.E.C. for 60° type copper conductors.

table 1. copper Wire Size

Grounding

WARnInG:

the unit cabinet must have an uninterrupted or

unbroken electrical ground to minimize personal

injury if an electrical fault should occur. Do not

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance

with local codes or, in the absence of local codes, with

the National Electrical Code (ANSI/NFPA 70) or the CSA

C22.1 Electrical Code. Use the grounding lug provided in

the control box for grounding the unit.

Blower Speed

The blower speed is preset (for operation) at the factory

for heating and cooling. These factory settings are listed

in

Table 5 (page 19)

. For optimum system performance

and comfort, it may be necessary to change the factory

set speed.

cAUtIon:

to avoid personal injury or property damage,

make sure the motor leads do not come into

contact with any uninsulated metal components

of the unit.

1. Shut off all electrical power to the unit and remove

the blower panel. Locate the orange and red wires

terminated to the blower motor.

notE: The orange wire

controls cooling operation while the red wire controls

heating operation.

2. Verify the required speed from the airflow data found

in

Table 5

. Place appropriate wire on the correct motor

speed tap for the required airflow point.

thermostat connections

• The Q6SE heat pump may require a 2-stage cooling /

heating thermostat if used in conjunction with certain

installed accessories. Refer to your manual for additional

instructions.

• The low voltage wires must be properly connected to

the units low voltage terminal block as shown in

Figure

7 (page 14)

. Recommended wire gauge and lengths

for typical thermostat connections are listed in

Table 2

(page 10)

.

• The

l terminal on the defrost control board is used for

fault monitoring. This is a 24V output and may be used

with compatible thermostats. Refer to the thermostat

manufacturer's manual to ensure compatibility.

FAIlURE to EnSURE coMPAtIBIlItY cAn lEAD

to tHERMoStAt FAIlURE.

• The thermostat should be mounted about 5 feet above

the floor on an inside wall. DO NOT install the thermostat

on an outside wall or any other location where its

operation may be adversely affected by radiant heat from

fireplaces, sunlight, or lighting fixtures, and convective

heat from warm air registers or electrical appliances.