beautypg.com

Heat pump maintenance, Charging an r-410a unit in ac mode, Charging an r-410a unit in heating mode – Reznor Q6SE Unit Installation Manual User Manual

Page 12: Replacement parts, Warning, Caution

background image

12

charging an R-410A Unit in Ac Mode

(With Outdoor Temperatures Above 65° F)

1. With the system operating at steady-state, measure the

liquid refrigerant pressure in psig at the service valve.

2. Measure the liquid refrigerant temperature in Fahrenheit

at the service valve.

3. For the temperature measured, determine the required

liquid refrigerant pressure from the appropriate charging

charts in

Figure 9

,

Figure 10 (page 16)

,

Figure 11

,

Figure 12 (page 17)

,

Figure 13

,

Figure 14 (page

18)

.

4. If the pressure measured in step 1 is greater than the

required liquid refrigerant pressure determined in step

4, then there is too much charge in the system. Remove

refrigerant and repeat steps 1 through 3 until the system

is correctly charged.

5. If the pressure measured in step 1 is less than the

required liquid refrigerant pressure determined in

step 4, then there is too little charge in the system.

Add refrigerant and repeat steps 1 through 3 until the

system is correctly charged.

charging an R-410A Unit in Heating Mode

1. Evacuate the refrigerant system.

2. Weigh in the proper charge based on the charge level

noted on the rating plate. Unit charge MUST be verified

in cooling season.

3. Verify the unit is operating properly as outlined in System

Heating (

page 11

).

REPlAcEMEnt PARtS

Replacement parts are available through your distributor.

Please have the complete model and serial number of

the unit when ordering replacement parts.

ElEctRIcAl:

• Capacitors

• Pressure Switches

• Cooil Sensor

• Relays

• Compressors

• Transformers

• Contactors

MotoRS:

• Blower Motor
• Fan Motor

coMPonEntS:

• Blower Assembly

• Fan Grille

• Cabinet Panels

• Filter/Driers

• Expansion Valves

HEAt PUMP MAIntEnAncE

WARnInG:

to prevent electrical shock, personal injury, or

death, disconnect all electrical power to the unit

before performing any maintenance or service.

Unit may have more than one electrical supply.

cAUtIon:

Use care when servicing the heat pump or

removing components. Personal injury can

result from sharp edges present in equipment

constructed with sheet metal

Proper maintenance is important to achieve optimum

performance from the heat pump. The ability to properly

perform maintenance on this equipment requires certain

mechanical skills and tools. If you do not possess these

skills, contact your dealer for maintenance. Consult your

local dealer about the availability of maintenance contracts.

Routine maintenance should include the following:

• Inspect and clean or replace air filters at the beginning

of each heating and cooling season, or more frequently

if required.

• Inspect the condensate drain and outdoor coil at the

beginning of each cooling season. Remove any debris.

Clean the outdoor coil and louvers as necessary using

a mild detergent and water. Rinse thoroughly with water.

• Inspect the electrical connections for tightness at the

beginning of each heating and cooling season. Service

as necessary.

cAUtIon:

the unit should never be operated without a

filter in the return air system. Replace disposable

filters with the same type and size.

• The motors for the circulating air blower and the outdoor

fan are pre-lubricated at the factory. No further oiling is

required for the life of this product.