beautypg.com

Electrical wiring, Pre-electrical checklist, Line voltage – Reznor Q6SE Unit Installation Manual User Manual

Page 8: Rooftop, Horizontal to downflow conversion, Condensate drain, Warning

background image

8

• Units require horizontal roof curb and return air kit for

horizontal installations.

• Ductwork should be attached directly to flanges on

panels supplied in horizontal duct conversion kits.

Rooftop

Rooftop installations must be located according to local

building codes or ordinances and these requirements:

• The roof must be capable of handling the weight of the

unit. For unit weights, see

Table 4 (page 13)

. Reinforce

the roof if necessary.

• The appropriate accessory roof curb (

Figure 4

) must be

installed prior to unit installation. The roof curb must be

square and level to ensure proper condensate drainage.

Please follow all instructions provided with the kit.

• Secure roof curb or frame to roof using acceptable

mechanical methods per local codes.

notE:

Make sure

the two supports beneath the unit have been removed.

Roof

Curb

Figure 4. Roof top Installation

Figure 5. condensate Drain location

ElEctRIcAl WIRInG

WARnInG:

to avoid risk of electrical shock, personal injury,

or death, disconnect all electrical power to the unit

before performing any maintenance or service.

the unit may have more than one electrical supply.
label all wires prior to disconnection when

servicing the unit. Wiring errors can cause

improper and dangerous operation

• Electrical connections must be in compliance with

all applicable local codes and ordinances, and with

the current revision of the National Electric Code

(ANSI/NFPA 70).

• For Canadian installations the electrical connections

and grounding shall comply with the current Canadian

Electrical Code (CSA C22.1 and/or local codes).

Pre-Electrical checklist:

√ Verify that the voltage, frequency, and phase of the

supply source match the specifications on the unit rating

plate.

√ Verify that the service provided by the utility is sufficient

to handle the additional load imposed by this equipment.

refer to the unit wiring label for proper high and low

voltage wiring.

√ Verify factory wiring is in accordance with the unit wiring

diagram. See

Figure 8 (page 15)

. Inspect for loose

connections.

line Voltage

• A wiring diagram is located on the inside cover of the

units electrical box. The installer should become familiar

with the wiring diagram before making any electrical
connections to the outdoor unit.

An electrical disconnect must be located within sight

of and readily accessible to the unit. This switch shall

be capable of electrically de-energizing the unit.

• Line voltage to the unit should be supplied from a

dedicated branch circuit containing the correct fuse

or circuit breaker for the unit. Incoming field wiring

Condensate

Drain

Horizontal to Downflow conversion

The unit is shipped ready for horizontal duct connections.

If down flow ducts are required, the unit must be converted

following the steps below for the supply and return ducts.

1. Locate the duct cap inside the duct openings and remove

the screw holding it in place.

2. Lift the cap out of the unit. (

Hint: The cap can be pushed

up from the bottom by reaching through the fork slot).

3. Cover the horizontal duct opening with the horizontal

duct cap. The insulation will be on the indoor side.

4. Fasten the cover with screws to seal.

condensate Drain

Condensate is removed from the unit through the 3/4”

female pipe fitting located on the front side of the unit.

Install a 2 inch condensate trap in the drain line of the

same size and prime with water. See

Figure 5

.

When connecting rigid drain line, hold the female fitting

with a wrench to prevent twisting.

Do not over tighten!

Refer to local codes and restrictions for proper condensate

disposal requirements.