beautypg.com

Start up & adjustments, Pre-start check list, Start-up procedure – Reznor Q6SE Unit Installation Manual User Manual

Page 11: Air circulation, Short cycle protection, System cooling, System heating, Refrigerant charging, Pre-start check list start-up procedure, Warning

background image

11

any unusual noises. If unusual sounds occur, determine

the source of the noise and correct as necessary.

3. Allow the cooling system to operate for several minutes

and then set the temperature selector above room

temperature. Verify the fan and compressor cycle off

with the thermostat.

notE: The blower should also

stop unless fan mode is set to ON.

System Heating

If the unit has been equipped with optional electric heater

kits, set the thermostat's system mode to HEAT and the

fan mode to AUTO. Verify the compressor and outdoor

fan are not energized but that the blower and heaters are.

Feel the air being circulated by the indoor blower and verify

that it is warmer than ambient temperature. Listen for any

unusual noises. If unusual sounds occur, determine the

source of the noise and correct as necessary.

REFRIGERAnt cHARGInG

WARnInG:

Single Packaged Heat Pumps are shipped fully

charged with R-410A refrigerant and ready

for installation. When a system is installed

according to these instructions, no refrigerant

charging is required. If repairs make it necessary

for evacuation and charging, it should only be

done by qualified, trained personnel thoroughly

familiar with this equipment. Some local codes

require licensed installation/service personnel

to service this type of equipment. Under no

circumstances should the owner attempt to

install and/or service this equipment. Failure to

comply with this warning could result in property

damage, personal injury, or death.

The system refrigerant charge can be checked and

adjusted through the service ports provided at the front

panel. Use only gauge lines which have a Schrader

depression device present to actuate the valve. Draw a

vacuum on gauge lines to remove air before attaching

them to the service ports on the unit.

IMPoRtAnt notES:

• To achieve rated capacity and efficiency the compressor

must be exposed to refrigerant for at least 24 hours prior

to running and then must be run for a minimum of 12

hours.

• The refrigerant charging charts are applicable to listed

assemblies of equipment and at listed airflows for the

indoor coil. Assemblies of indoor coils and outdoor units

not listed are not recommended. See

Figure 9

,

Figure 10

(page 16)

,

Figure 11

,

Figure 12 (page 17)

,

Figure

13

,

Figure 14 (page 18)

.

StARt UP & ADjUStMEntS

Pre-Start check list

√ Verify the unit is level and allows condensate to drain.

√ Verify the outdoor coil and top of the unit are free from

obstructions and debris, and all equipment access/

control panels are in place.

√ Verify that the duct work is sealed to prevent air leakage.

√ Verify that the line voltage power leads are securely

connected and the unit is properly grounded.

√ Verify that the low voltage wires are securely connected

to the correct leads on the low voltage terminal strip.

√ Verify that the outdoor fan turns freely.

√ Verify that the power supply branch circuit overcurrent

protection is sized properly.

√ Verify that the thermostat is wired correctly. The

thermostat system mode should be set to OFF and the

thermostat fan mode should be set to AUTO.

Start-Up Procedure

Close all electrical disconnects to energize the system.

cAUtIon:

If the unit is equipped with a crankcase heater,

allow 24 hours prior to continuing the start up

procedures to allow for heating of the refrigerant

compressor crankcase. Failure to comply may

result in damage and could cause premature

failure of the system. this warning should be

followed at initial start up and any time the power

has been removed for 12 hours or longer.

Air Circulation

Leave the thermostat system mode on OFF, and set the

fan mode to ON. Blower should run continuously. Check

the air delivery at the supply registers and adjust register

openings for balanced air distribution. Examine ductwork

for leaks or obstruction if insufficient air is detected. Set

the thermostat fan mode to AUTO. The blower should

stop running.

Short Cycle Protection

1. With the system operating in cooling mode, note the

temperature setting of the thermostat and gradually raise

the set-point temperature until the unit de-energizes.

2. Immediately lower the set point temperature of the

thermostat to its original setting and verify that the

indoor blower is energized.

3. After approximately 5 minutes, verify the compressor

and fan energize and the temperature of the discharge
air is cooler than the room temperature.

System Cooling

1. Set the thermostat’s system mode to COOL and the

fan mode to AUTO. Gradually lower the thermostat

temperature setpoint below room temperature and

verify the outdoor unit and indoor blower energize.

2. Feel the air being circulated by the indoor blower and

verify that it is cooler than ambient temperature. Listen for