air conditioner Maintenance

Warning:

electrical SHock or Fire HaZard

Failure to follow safety warnings exactly could

result in serious injury or property damage.
improper servicing could result in dangerous

operation, serious injury, death or property

damage.
• Before servicing, disconnect all electrical

power to furnace.

• When servicing controls, label all wires prior

to disconnecting. reconnect wires correctly.

• Verify proper operation after servicing.”

avertiSSeMent :

riSQue de dÉcHarge ÉlectriQue

ou d’ d’incendie

le non-respect des avertissements de sécurité

pourrait entraîner un fonctionnement dangereux

de l’appareil, des blessures graves, la mort ou des

dommages matériels.
un entretien incorrect pourrait entraîner un

fonctionnement dangereux de l’appareil, des

blessures graves, la mort ou des dommages

matériels
• Couper toute alimentation électrique au générateur

d’air chaud avant de procéder aux travaux

d’entretien.

• Au moment de l’entretien des commandes,

étiqueter tous les fils avant de les débrancher.

S’assurer de les raccorder correctement.

• S’assurer que l’appareil fonctionne adéquatement

après l’entretien.

Proper maintenance is important to achieve optimum

performance from the air conditioner. The ability to properly

perform maintenance on this equipment requires certain

mechanical skills and tools. If you do not possess these

skills, contact your dealer for maintenance. Consult your

local dealer about the availability of maintenance contracts.

Routine maintenance should include the following:

• Inspect the condensate drain and outdoor coil at the

beginning of each cooling season. Remove any debris.

Clean the outdoor coil and louvers as necessary using a

mild detergent and water. Rinse thoroughly with water.

• Inspect the electrical connections for tightness at the

beginning of each heating and cooling season. Service

as necessary.

• Inspect and clean or replace air filters at the beginning

of each heating and cooling season, or more frequently

if required.

caution:

the unit should never be operated without a

filter in the return air system. replace disposable

filters with the same type and size.

• The motors for the circulating air blower and the outdoor

fan are pre-lubricated at the factory. No further oiling is

required for the life of this product.

reFrigerant cHarging

Warning:

Single Packaged air conditioners are shipped

fully charged with r-410a refrigerant and ready

for installation. When a system is installed

according to these instructions, no refrigerant

charging is required. if repairs make it necessary

for evacuation and charging, it should only be

done by qualified, trained personnel thoroughly

familiar with this equipment. Some local codes

require licensed installation/service personnel

to service this type of equipment. under no

circumstances should the owner attempt to

install and/or service this equipment. Failure to

comply with this warning could result in property

damage, personal injury, or death.

The system refrigerant charge can be checked and

adjusted through the service ports provided at the front

panel. Use only gauge lines which have a Schrader

depression device present to actuate the valve. After

refrigerant line connections are completed, leak check

and evacuate the indoor section and all line connections

(using proper methods) before finalizing the full system

refrigerant charge.
• P8SE outdoor units with non-AHRI listed indoor coils

are not recommended. Deviations from rated airflows or

non-listed combinations may require modification to the

expansion device and refrigerant charging procedures

for proper and efficient system operation.

• The refrigerant charge can be checked and adjusted

through the service ports provided external to the outdoor

unit. Use only gage line sets which have a “Schrader”

depression device present to actuate the valve.

• A high-pressure switch is factory-installed and located

in the liquid line internal to the outdoor unit. The switch

is designed to protect the system when very high

pressures occur during abnormal conditions. Under

normal conditions, the switch is closed. If the liquid

pressure rises above 650 psig, then the switch will open

and de-energize the outdoor unit. The switch will close

again once the liquid pressure decreases to 460 psig.

Please note that the switch interrupts the thermostat

inputs to the unit. Thus, when the switch opens and

then closes, there may be a 5 minute short cycling delay

before the outdoor unit will energize.