AIRFLOW INFORMATION
Table 12. Airflow Settings (CFM) & Rise (° F) for Heating Operation Mode
Table 11. Airflow Settings for Cooling
Table 10. Nominal Airflow Rates & Temperature Rises (° F)
Model Number
Heating Input
(btuh)
Heating Output
(btuh)
CFM Range
Heating Rise
Range (°F)
Cooling Output
(btuh)
Blower
Size
Motor
(HP)
X24K080CA
80,000
64,000
1100 - 1350
35-65
24,000
10 X 10
1/2
52,000
41,600
750 - 1050
X36K100CA
100,000
80,000
1200 - 1600
40-70
35,000
10 X 10
1/2
65,000
52,000
900 - 1200
X48K120CA
120,000
96,000
1350 - 2000
40-70
46,000
11 X 10
1
78,000
62,400
950 - 1300
X60K120CA
120,000
96,000
1350 - 2000
40-70
55,500
11 X 10
1
78,000
62,400
950 - 1300
NOTE: CFM and Rise are independent of ESP in a variable speed blower.
2 TON UNITS
3 TON UNITS
4 - 5 TON UNITS
BLOWER
SELECTOR
SETTING
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
BLOWER
SELECTOR
SETTING
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
BLOWER
SELECTOR
SETTING
RECOMMENDED
A/C AIRFLOW
RATE (CFM)
COOL
ADJUST
COOL
ADJUST
COOL
ADJUST
TAP “A”
-10%
2
T
O
N
685
TAP “A”
-10%
840
TAP “A”
-10%
4
T
O
N
1485
Normal
760
Normal
3
T
O
N
930
Normal
5
T
O
N
1650
+10%
835
+10%
1025
+10%
1815
TAP “b”
-10%
840
TAP “b”
-10%
975
TAP “b”
-10%
1620
Normal
930
Normal
1080
Normal
1800
+10%
1025
+10%
1190
+10%
1980
TAP “C”
-10%
975
TAP “C”
-10%
1110
TAP “C”
-10%
1665
Normal
1080
Normal
1230
Normal
1850
+10%
1190
+10%
1350
+10%
2035
TAP “D”
-10%
1110
TAP “D”
-10%
1290
TAP “D”
-10%
1800
Normal
1230
Normal
1430
Normal
2000
+10%
1350
+10%
1575
+10%
2200
Blower HEAT
Selector Setting
2 TON
3 TON
4 & 5 TON
Low Input
High Input
Low Input
High Input
Low Input
High Input
52,000
80,000
65,000
100,000
78,000
120,000
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
CFM
Rise
TAP “A”
750
51
1100
55
900
53
1200
63
950
61
1350
67
TAP “B”
850
45
1150
53
1000
48
1300
58
1050
55
1500
61
TAP “C”
950
41
1250
49
1100
44
1400
54
1150
50
1700
54
TAP “D”
1050
37
1350
45
1200
40
1600
47
1300
44
2000
46
NOTES:
1. Recommended temperature rises are highlighted in
bold
. Use of any other setting may result in nuisance trips.
2. Temperature rises in the table are approximate. Actual temperature rises may vary.
3. blower “ADJUST” tap non-functional in Heating mode.