beautypg.com

Electrical connections, Warning: disconnect power to the unit – Reznor RBL Option - Installation - Evaporative Cooling Option User Manual

Page 7

background image

Mfg No. 160202, Page 7

7. Electrical

Connections

Line voltage wiring must be field installed between the blower junction box and the
evaporative cooling module junction box. The tubing-encased wires are factory-
connected in the cooling module junction box.
NOTE:

Models ADF/ADFH have only 115V optional evaporative cooling module

pumps. A transformer is included on the unit.

FIGURE 9A - Diagram of
Evaporative Cooling
Module Factory-Installed
Wiring -- “BL” Models
with 115/230/1/60 or 230/
460/575/3/60 (Heater
Options AK3, 6, 7 or 8) and
Models ADF/ADFH 700/
1200 (see Note above)

FIGURE 9B - Diagram of
Evaporative Cooling
Module Factory-Installed
Wiring -- Systems with 208/
1-3/60 (Heater Option AK2
or AK5)

V

W

PUMP MOTOR

LINE VOLT

SWITCH

FLOAT

W

BK

H

BK

J

Y

N.O. TWO WAY

DRAIN VALVE

FILL VALVE

THREE WAY

OPTIONAL

OPTIONAL

Y

115-230/1/60

COOLING CIRCUIT

111145 REV #4

EVAPORATIVE COOLING MODULE

BK

N.O. TWO WAY

DRAIN VALVE

FILL VALVE

THREE WAY

OPTIONAL

OPTIONAL

208/1/60

COOLING CIRCUIT

111452 REV #4

BK

PUMP MOTOR

230 VOLT

FLOAT

SWITCH

V

Y

W

H

W

BK

BUCK-BOOST

40 VA. TRANSFORMER

BK

I

Y

J

R

BK

BL

BR

Y

EVAPORATIVE COOLING MODULE

Y

Instructions for
“Internal Field-
Required Wiring
From Cooling Module
to System Cabinet

WARNING: Disconnect
power to the unit.

NOTE:

The two snap strain relief bushings are shipped in the bottom pan of the

cooling module.
1. Remove the compartment door panels and electrical compartment cover.

Remove the service panel in line with the hole in the cooling module.

2. Drill a 7/8" hole in the cabinet end panel in line with the hole in the cooling

module junction box.

3. Pull the tubing-encased wires through the hole in the blower cabinet. Place the

strain relief bushings around the tubing and insert the bushing into the hole
(Bushing must be used to prevent water from leaking into the cabinet). Route
the wires across the cabinet bottom. If there are any filters, run the wires
through the slot in the bottom filter rack. If there are inlet dampers, be careful
that the wires do not interfere with the damper controls. Run the wires up to
the electrical compartment, remove a plug from one of the bottom entrance
hole, and push the tubing-encased wires into the electrical compartment. Place
the other strain relief bushing around the tubing and insert the bushing into the
hole in the electrical compartment.

4. Follow the wiring diagram included with the heater to properly connect the

wires to the terminal blocks. If there is excess tubing and/or wiring, trim
before making connections.

5. Before unit is operated, replace all door panels and fasten all latches.