Components - options cw 8, 9, 10, Step 5 vertical (top) inlet - final steps, Step 4 horizontal inlet - install filters – Reznor CAUA Option - Installation - Filter Cabinet User Manual
Page 8

Form I-CAUA-FC, Page 8
NOTES:
* Application requires 2" permanent filters; do not use pleated filters.
** If installing filter cabinet that attaches to the side of the heater (Option
CW 4, 5, or 6), two cabinets must be installed, one on each side.
SMALL RETURN AIR FILTER CABINET FOR ATTACHING TO REAR OR SIDE
OF MODEL CAUA 150 OR 200 - OPTIONS CW 8, 9, 10
STEP 5 Vertical (Top) Inlet - Final
Steps
Parts Required: Door Assembly
Instructions:
Install the door on the end of the filter
cabinet. Fasten the latches.
Installation of the optional filter cabinet
with a vertical (top) inlet is complete.
Duct flange dimensions for connecting
ductwork are shown on page 6.
After heater installation is complete and
return air ductwork is connected, turn
on the electric and the gas and check
for proper operation.
STEP 4 Horizontal Inlet - Install Filters
Parts Required: Filters (either shipped with the option package or
field-supplied)
Instructions: Slide the filters into the filter rack channels.
Permanent or Pleated 2" Filters
for Options CW4, CW5, or CW6
Size CFM FPM
Filters
150
1800
281
(4) 16 x 16
2400
375
(4) 16 x 16
3000
469
(4) 16 x 16
200
2400
375
(4) 16 x 16
3000
469
(4) 16 x 16
250
3000
469
(4) 16 x 16
*4000
625
(4) 16 x 16
**5000
781
(4) 16 x 16;
(4) 16 x 16
300
3000
469
(4) 16 x 16
*4000
625
(4) 16 x 16
**5000
781
(4) 16 x 16;
(4) 16 x 16
350
4300
448
(6) 16 x 16
5000
521
(6) 16 x 16
*6000
625
(6) 16 x 16
400
4300
448
(6) 16 x 16
5000
521
(6) 16 x 16
*6000
625
(6) 16 x 16
Permanent or Pleated 2"
Filters for Options CW7,
CW12, or CW11
Size CFM FPM
Filters
150
1800
281
(4) 16 x 16
2400
375
(4) 16 x 16
3000
469
(4) 16 x 16
200 2400
375
(4) 16 x 16
3000
469
(4) 16 x 16
250
3000
313
(6) 16 x 16
4000
417
(6) 16 x 16
5000
521
(6) 16 x 16
300
3000
313
(6) 16 x 16
4000
417
(6) 16 x 16
5000
521
(6) 16 x 16
350
4300
448
(6) 16 x 16
5000
521
(6) 16 x 16
*6000 625
(6) 16 x 16
400
4300
448
(6) 16 x 16
5000
521
(6) 16 x 16
*6000 625
(6) 16 x 16
Filter
Cabinet
Door Panel
Assembly
Components -
Options CW 8, 9, 10
Rear and side filter
cabinets, Options CW 8,
9, and 10, are shipped
separately for field
assembly and installation.
(The cabinets are
assembled as they are
installed.) The table on the
right lists the Package P/N's
and the components in
each package by package
P/N and by Model Size.
Before beginning
installation, verify that all
parts are available at the
job site.
Filter Cabinet Components by Option Package - CW Options that attach to rear or side
For Model CAUA
Sizes 150 and 200
Option CW8 (with 2" pleated filters) - Pkg P/N
166159
Option CW9 (with 2" permanent filters) - Pkg P/N
166160
Option CW10 (for field-supplied 2" filters) - Pkg P/N
166161
Component Description
Filter cabinet attaches to side or rear of
heater with horizontal (rear) inlet only
Qty
P/N
Bottom Panel
1
164537
Side Panel
1
164536
Rear or Top Inlet Panel (w/duct flange)
1
164533
Top Panel or Bottom Rear Panel
1
164537
Door Panel Assembly
1
166148
Door Channel
1
164535
Filter Support
2
164704
Filter Support Channel
2
164532
Filter Channel Assembly
1
166147
Sheetmetal Screws #10-32 x 1/2" long
20
113275
2" Permanent Filters * in Option CW9
4
114325
2" Pleated Filters * in Option CW8
2
114324
*See Step 5, page 11 for filter dimensions.