beautypg.com

Installation instructions warning – Reznor VR Option - Installation - Multiple Heater Control (Options CL31 and CL32) User Manual

Page 3

background image

Form I-OPT-MH, P/N 102247 R7, Page 3

Pressure Switch

- Sizes 30-125

Venter Motor (Size 30-75

illustrated. Venter motor is in the

same location for all models,

but appearance is different.)

Fan

Motor

Gas Valve

TRANSFORMER

Circuit Board

(DSI Integrated

Control Module)

Optional Fan Motor

Capacitor (used with

208/230V and Option AL14)

High Temperature

Limit Control

Flame Rollout Switch

(UDAP and UDAS

Sizes 30-125 only)

Ignitor

Flame

Sensor

Burner

Assembly

Terminal

Board (24V)

TRANSFORMER

Circuit Board

(DSI Integrated

Control Module)

Fan Motor

Capacitor

Venter Motor

Capacitor

Pressure Switch

(Sizes 150-400)

Control Panel Assy

located on the

Control Compartment

Bottom

UDAP/S 30-125

UDAP/S 150-400

All UEAS - On the cabinet

bottom; control locations

are slightly different.

UDAS, UEAS, and

UDBS have a collar

for the combustion

air pipe (not shown)

Door Switch - UDAS,

UEAS, and UDBS only

Electrical Box - UDAS

and UDBS only

Remove cover to connect

supply and access discon-

nect switch wires. Always

replace cover.

Disconnect Switch

- UDAS, UEAS, and

UDBS only

FIGURE 1A - Control Compartment showing Transformer Location, Models UDAP, UDAS, and UEAS

"Primary" Heater

The transformer is mounted on the control board on the bottom of the control compartment.

These instructions are designed to assist a qualified electrician in installing this multiple

heater control kit. All electrical wiring and connections, including electrical grounding,

MUST be in accordance with the National Electric Code ANSI/NFPA No. 70 (latest edi-

tion) or, in Canada, with the Canadian Electrical Code, Part 1-C.S.A. Standard C22.1 In

addition, the installation must comply with local ordinances and applicable gas company

requirements.
Follow the instructions that apply to the option and model of heater.
1. Turn off the gas and electric power.
2. Change the Transformer (does not apply to Model LDAP, UDBP, or UDBS) –

applies to OPTION CL31 installation on the "Primary" unit only

Refer to the illustration

(FIGURE 1A, 1B, or 1C) for the unit being serviced.

Remove or open panels as required and locate the factory-installed transformer.

Mark and disconnect the wires. Remove the transformer.
Using the same screws (except Models F and B; see

FIGURE 1C), install the 35 or

40 VA transformer from the kit. Connect the wires. Close the panel.

Installation

Instructions

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property

damage, injury, or death. Read the installation, operation, and maintenance instructions

thoroughly before installing or servicing this equipment.