Reznor VR Option - Installation - Multiple Heater Control (Options CL31 and CL32) User Manual
Description/ application, Kit components by model

Form I-OPT-MH, P/N 102247 R7, Page 1
Applies to:
Reznor
®
Models LDAP, UDAP, UDAS,
UDBP, UDBS, UEAS, F, B, VR
Description/
Application
These options are designed to permit the control of up to six heaters (one "Primary" heater
and one to five "Secondary" units; see note for LDAP limitations) with one single-stage ther-
mostat or with a time clock and single or multiple single-stage thermostats. For maximum
safety, the multiple control is done in the low voltage circuit. (Interruption of the supply volt-
age is not recommended.) Wiring lengths may not exceed those shown in the table on page
8.
DO NOT use these multiple heater control options with a two-stage gas valve or a
two-stage thermostat.
Kit Components
by Model
Check the components
against the list for the
model being installed.
•
Model LDAP
•
Model UDAP
•
Model UDAS
•
Model UDBP
•
Model UDBS
•
Model UEAS
•
Model F
•
Model B
•
Model VR
Installation of Multiple Heater Control, Options CL31 and CL32
Form I-OPT-MH (Version D)
Obsoletes Form I-OPT-MH (Version C)
Application
by Voltage
& Model
Model LDAP
Models UDAP,
UDAS, UDBP,
UDBS, and UEAS**
Models F, B, and VR
Application
by Voltage
& Model
115/1
N/A
CL31 for both the
Primary and 1st
Secondary Heater
plus a CL32 each
for the 2nd, 3rd, 4th,
and 5th Secondary
Heaters.
CL31 for both the Primary and 1st
Secondary plus a CL32 each for 2nd,
3rd, 4th, and 5th Secondary Heaters.
115/1
208/1
CL31 for both the Primary
and 1st Secondary Heater
plus a CL32 each for the
2nd, 3rd, 4th, and 5th
Secondary Heaters. *
CL32 for the Primary Heater plus
CL32 each for 1st, 2nd, 3rd, 4th, and
5th Secondary Heaters.
208/1
230/1
230/1
208/3
N/A
208/3
230/3
N/A
230/3
460/3
N/A
460/3
575/3
N/A
CL31 for both the Primary and 1st
Secondary plus a CL32 each for 2nd,
3rd, 4th, and 5th Secondary Heaters.
575/3
* Model LDAP 400 can have five secondary heaters; Model LDAP 800 can have a maximum of three secondary
heaters; and Model LDAP 1200 can have a maximum of two secondary heaters.
** Model UEAS is 115 volt only.
Kits for Model LDAP
Option CL31 for LDAP -
Pkg P/N 208366 for Primary and One Secondary Unit
Qty
P/N
Description
2
208365 Relay Assemblies each consisting of one P/N 18549 relay, with attached
42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with
terminals.
2
208185 Wiring Diagram Label
Option CL32 for LDAP -
Pkg P/N 208367 for each Additional Secondary Unit
Qty
P/N
Description
1
208365 Relay Assemblies each consisting of one P/N 18549 relay, with attached
42" red wire, 42" white wire, 6" blue wire, and 6" brown wire -- all with
terminals.
1
208185 Wiring Diagram Label
Kits for Models UDAP, UDAS, UDBP, UDBS, UEAS
Opt CL31 for UDAP/UDAS/UEAS -
Pkg P/N 197155 for Primary & One Secondary Heater
Qty
P/N
Description
1
194808 Transformer 40VA
2
197157 Relay Assemblies each consisting of one P/N 18549 relay, wired and
mounted on a specially designed bracket.
2
195249 Self-drilling screw for attaching relay bracket
2
16228 Cable Clamp 3/16"
2
197164 Wiring Diagram Label
1
197160 Wiring Harness Assembly (brown wires)
- B Option - Installation - Multiple Heater Control (Options CL31 and CL32) F Option - Installation - Multiple Heater Control (Options CL31 and CL32) UEAS Option - Installation - Multiple Heater Control (Options CL31 and CL32) UDBS Option - Installation - Multiple Heater Control (Options CL31 and CL32) UDBP Option - Installation - Multiple Heater Control (Options CL31 and CL32) UDAS Option - Installation - Multiple Heater Control (Options CL31 and CL32) UDAP Option - Installation - Multiple Heater Control (Options CL31 and CL32) LDAP Option - Installation - Multiple Heater Control (Options CL31 and CL32)