Day / night schedule, Set time, History – LAARS M4-Ext - Installation Manual User Manual
Page 28: Maintenance, Mini-mod, Alert, A b c d, 00 am, Day/night schedules, 35 pm
28
dAY / NigHT SCHEdULE
DAY/NIGHT SCHEDULE
Set Time
**:**
Day Schedule 6:00a
Night Schedule
8:00p
BACK ▲ ▼ SAVE
-- DAY SCHEDULE --
6:00 Am
BACK ▲ ▼ SAVE
dAY/NigHT SCHEdULES
(Available when "Shutdown or Tstat" is selected from the Shutdown/
Tstat/Setback Startup menu option only)
Button: MENU/
• The M4-CNC has two levels of heat. The Day (Normal) level is used when a building is
occupied and people are active.
• The Night (Setback) level is used when a building is not occupied, or when people are
sleeping. This setting reduces the calculated temperature by the Setback setting. See
"Setback" on page 24. If the Day calculated water temperature was 150˚F and the Setback
was 20˚F, the Night Schedule will run at (150˚F - 20˚F) = 130˚F.
• If the Boost feature is being used, it uses the Day Schedule as the Boost ending point. See "Boost Mode" on page 20. That is, if the
Day Schedule is set to start at 6:00AM, the Boost will start 30 minutes prior to the Day setting at 5:30AM. The M4-CNC will then
raise the calculated water temperature by the Setback amount. Using the previous example, at 5:30AM the M4-CNC will raise the
calculated water to 170˚F = (150˚F + 20˚F) until 6:00AM.
SET TiME
Button: MENU/
• Adjust the time by selecting Set Time from the menu and then scrolling through the hours
then select Save. Then, scroll through the minutes then select Save. If the hours are to be
set to PM, scroll through the AM hours to reach the PM hours.
----- SET TIME -----
7:35 Pm
BACK ▲ ▼ SAVE
ALERT
Remember that the battery is the backup for the Time. If no power is supplied to the
M4-CNC and
there was no battery or the battery had no power, time values will be lost and will need to be reset.
HiSTORY
Button: MENU/
The M4-CNC provides users with a graphical history of the System and Outdoor temperatures for
the previous 24 hours. The temperatures are sampled every 12 minutes. That is, readings of both
System and Outdoor temperatures are recorded and stored every 12 minutes for the last 24 hours.
• To view the values of specific time period, use the two middle buttons to scroll to that time
and read the upper left temperature.
• The first screen will be the System Temperature History. By clicking on the Next button,
you'll be able to view the Outdoor Temperature History.
----------- SETTINGS ------------
Winter
Set Point
70 F
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
70
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
70
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
240
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
----------- SETTINGS ------------
Season
Winter
Set Point
70 F
BACK
SELECT
BACK
SAVE
------------- SEASON --------------
Winter
Summer
BACK
SAVE
------------ SET POINT ----------
70
F
[
]
--------- RESET RATIO ----------
1.00 OD=4.00 Sys
1.00 OD=3.00 Sys
1.00 OD=2.00 Sys
1.00 OD=1.50 Sys
1.00 OD=1.25 Sys
1.00 OD=1.00 Sys
1.25 OD=1.00 Sys
1.50 OD=1.00 Sys
2.00 OD=1.00 Sys
3.00 OD=1.00 Sys
4.00 OD=1.00 Sys
BACK
SAVE
BACK
START
-------- SYSTEM STARTUP ------
(START)
to continue
BACK
CONTINUE
------------- WARNING ------------
THESE SETTINGS
CHANGE PRIMARY
SYSTEM FUNCTIONS.
-------- ARE YOU SURE? -------
No
Yes
---------- SENSOR TYPE ---------
Set Point F
Set Point C
Reset F
Reset C
----- SETBACK/SHUTDOWN -----
Shutdown/Disable
Tstat/Enable
Setback
STARTUP
Reset Ratio
Set Point
BACK
SAVE
------- OUTDOOR CUTOFF -------
[
]
-------------- OFFSET -------------
+0
F
[
]
BACK
SAVE
--- MINIMUM WATER TEMP ----
70
F
[
]
BACK
SAVE
--- MAXIMUM WATER TEMP ----
240
F
[
]
Reset Ratio
BACK
SAVE
Shutdown or TStat Input
Setback Input
HISTORIES
--- SYS= 91 F, 10:57Am ---
--- OD= 54 F, 11:36Am ---
------ EMS INPUT MODE -------
Disable
Enable
Reset Options
Set Point
----- EMS 4ma SETPOINT-----
120
F
[
]
------ EMS 20ma SETPOINT-----
220
F
[
]
---------- BOOST MODE ---------
30 Minutes
Disabled
BACK
SAVE
--------- SENSOR FAULT --------
All Off
All On
BACK
SAVE
------- OUTPUT D TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
----- PROVE/DHW SHARING ----
Prove
DHW Priority
DHW No Priority
No Priority (Summer)
BACK
SAVE
------ MODULATION MODE ------
Normal
Parallel
BACK
SAVE
BACK
SAVE
BACK
SAVE
------- OUTPUT A TYPE --------
4-20ma
0-10v
0-5v
2-10v
1-5v
BACK
SAVE
BACK
SAVE
BACK
SAVE
BACK
EXIT
BACK
NEXT
BACK
SAVE
BACK
SAVE
Enabled
BACK
SAVE
------- DHW SETPOINT -------
180
F
[
]
Disabled
MAiNTENANCE
Button: MENU/
The Maintenance menu gives access to sensor and outputs trimming. In addition, you'll have
access to view the Startup configuration settings.
ALERT
To be able to change the
M4-CNC settings the Program/Run Switch must be set
to Program. The switch is located under the Enclosure Wiring Cover for security.
The Enclosure Wiring Cover can be securely closed using a lock.
----- MAINTENANCE ----
System Trim
+0
o
F
Outdoor Trim
0
o
F
BACK ▲ ▼ SAVE
SYSTEM
A
B
C
D
Full Modulation Sequencing Control
1 2
RUN
PROGRAM
FOR ALL CIRCUITS
120VAC, 6A RESISTIVE
OUTPUT RATINGS:
1A PILOT DUTY, 15A TOTAL
115VAC 60Hz , 12VA MAX
INPUT RATINGS:
USE COPPER CONDUCTORS ONLY
DO NOT APPLY ANY VOLTAGE
TO INPUT TERMINALS
3 4 5 6 7 8 9 10 11 12
13
15
14
17
16
18
22
20
19
21
24
23
29
25
27
26
28
32
30 31
L N
-
+
+
T
T
O
O
RS-485
mA
GND
VLT
SYS
A
B
C
D
PWR
CUR / VLT
A
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
-
+
+
mA
GND
VLT
+
mA
TEMP
OUTDOOR
O
O
TEMP
SYSTEM
EXTENSION
MODULE
CUR / VLT
B
CUR / VLT
C
CUR / VLT
D
CAUTION
: RISK OF ELECTRIC SHOCK
More than one disconnect switch may be required
to de-energize the equipment before servicing.
PROVE
/DHW
SHUTDOWN
/TSTAT
/SETBACK
ENCLOSED
ENERGY
MANAGEMENT
EQUIPMENT
99RA
Mini-MOD
LAARS Heating Systems
HT# 059104-00 B