OPERATiNg MENU SEqUENCE
ALERT
To be able to change the
M4-CNC
settings the Program/Run Switch
must be set to Program. The switch
is located under the Enclosure Wiring
Cover for security. The Enclosure
Wiring Cover can be securely closed
using a lock.
-------- SETTINGS ----
Season
Winter
System Target 140
o
F
BACK ▲ ▼ SELECT
OD=
55
o
F SYS=
143
o
F
<>
B
67%
22%
STAGE ◄ ► MENU
----- SEASON -----
Winter
Summer
BACK ▲ ▼ SAVE
-- SYSTEM TARGET --
1.00
o
OD = 4.00
o
Sys
1.00
o
OD = 3.00
o
Sys
1.00
o
OD = 2.00
o
Sys
1.00
o
OD = 1.50
o
Sys
1.00
o
OD = 1.25
o
Sys
1.00
o
OD = 1.00
o
Sys
1.25
o
OD = 1.00
o
Sys
1.50
o
OD = 1.00
o
Sys
2.00
o
OD = 1.00
o
Sys
3.00
o
OD = 1.00
o
Sys
4.00
o
OD = 1.00
o
Sys
BACK ▲ ▼ SAVE
----- SETTINGS 1 ----
Setback
0
o
F
Purge Delay 1.0min
System Run-On 0min
Lead Rotation Time
BACK ▲ ▼ SELECT
------- SETBACK -------
5
o
F
[
]
BACK ▲ ▼ SAVE
--- PURGE DELAY ---
1.0 min
[
]
BACK ▲ ▼ SAVE
-- SYSTEM RUN-ON --
5 min
[
]
BACK ▲ ▼ SAVE
-- LEAD ROTATION --
Manual
Time
Last-On
BACK ▲ ▼ SAVE
----- SETTINGS 2 ----
Standby Time 10min
Last Stg Hold 0
o
F
BACK ▲ ▼ SELECT
-- STANDBY TIME --
10 min
[
]
BACK ▲ ▼ SAVE
LAST STAGE HOLD
0
o
F
[ ]
BACK ▲ ▼ SAVE
--- LEAD STAGES ---
Cond Lead
A
Non-Cond Lead
C
BACK ▲ ▼ SAVE
- STAGE SETTINGS -
Reaction Time 2min
Minimum Runtime
2min
BACK ▲ ▼ SAVE
MODULATION SETTINGS
Gain
+0
Lag Delay
0min
Soft-Off Delay 45sec
BACK ▲ ▼ SAVE
DAY/NIGHT SCHEDULE
Set Time
**:**
Day Schedule 6:00a
Night Schedule
8:00p
BACK ▲ ▼ SAVE
------- OFFSET ------
+0
o
F
[ ]
BACK ▲ ▼ SAVE
- OUTDOOR CUTOFF -
65
o
F
[
]
BACK ▲ ▼ SAVE
MINIMUM WATER TEMP
70
o
F
[ ]
BACK ▲ ▼ SAVE
MAXIMUM WATER TEMP
240
o
F
[
]
BACK ▲ ▼ SAVE
LAARS Modulating Controls M4 & M4-EXT