2e. clearance / closet installations, Laars heating systems – LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual
Page 8
LAARS Heating Systems
Page 8
Special attention should be paid to clearances
between the front of the boiler and the closet door
when it is closed.
Consult the American National Standard Z21.13 for
more information concerning closet installations. In
Canada, refer to the latest edition of CSA-B149.1.
Figure 2JVS. Closet Installation
Dimensions in inches cm.
6 15
6 15
6 15
4*
10
*6" for models JV160 to JV225.
width and depth of the heater by at least 12 inches
(305mm) in all directions. The masonry must be laid
with ends unsealed, and joints matched to provide
free circulation of air from side to side through the
masonry (see Figure 1). If the boiler is installed in a
carpeted alcove, the entire floor of the alcove must be
covered by a noncombustible platform.
2E. Clearance / Closet Installations
All Mini-Therm JV's can be installed in a closet as
long as the minimum clearances are observed.
See
Table 2JVH and Figure 2JVH for
clearances required for the Mini-Therm JVH.
See
Table 2JVS and Figure 2JVS for
clearances required for the Mini-Therm JVS
Figure 2JVH. Closet Installation.
TOP
VIEW
SIDE
VIEW
2
(51)
A
2
(51)
5
(127)
6
(152)
6
(152)
MIN
Dimensions in
inches (mm).
Air
Openings
B
Note: Clearances listed are manufacturer’s tested values. These are given as minimum values. Where local and national
codes apply, and values are different than those listed use the greater value to ensure safe operation.
Minimum Boiler Clearances from Combustible Surfaces.
Dégagements Minimaux à Assurer Entre Ics Parois de L’appareil et leo Constructions Combustibles
Boiler Sizes
50 - 225
Clearances
in cm
Left side
2 5
Right side
5 15
Rear
2 5
Front
4 10
Flue
(using B-vent)
6 15
Top
23 58
Boiler Sizes
50 - 125
160 - 225
Clearances
in cm
in cm
Left side
6 15
6 15
Right side
6 15
6 15
Rear
6 15
6 15
Front
4 10
4 10
Flue
6 15
6 15
Top
23 58
36 91
Table 2JVS Minimum Boiler Clearances
Table 2JVH Minimum Boiler Clearances