beautypg.com

LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual

Page 14

background image

LAARS Heating Systems

Page 14

Figure 8. Gas Supply Piping.

HORIZONTAL

DROP

TO BOILER

SEDIMENT TRAP

OR DRIP LEG

TO BOILER

RISER

SEDIMENT TRAP

OR DRIP LEG

3" (76mm)

MIN.

3" (76mm)

MIN.

1. Gas piping installation must be in accordance

with the latest edition of ANSI Z223.1 and all

local codes. In Canada, the installation must be in

accordance with CSA-B149.1 and all local codes

that apply.

2. Check the gas supply to be sure that it is the

same as the gas indicated on the boiler’s plate.

Mini-Therm JVS and JVH boilers, as shipped

from the factory, are certified to operate within

the altitude range indicated on the rating plate.

If a field conversion to a different altitude range

or different gas should be necessary, conversion

parts are available. Contact a Laars representative

or the factory for the correct part numbers to

order for conversions

Caution

Permanent damage to the gas valve will occur

if the following procedures are not followed.

Attention

Vous endommagerez la soupape de gaz

si vous ne respectez pas les procédures

suivantes.

3. Use the figures in Table 6 to size the gas inlet

piping from the gas meter to the heater. Check all

local codes for compliance before installing the

heater.

Boiler Size

Distance

From Gas

Meter

50

75

100

125

160

225

Pipe Size

0-50

0-15m

1/2

3/4

3/4

3/4

1

1

50-100'

15-30m

3/4

3/4

3/4

1

1

1-1/4

100-200'

30-60m

3/4

1

1

1

1-1/4 1-1/4

*

Note: These figures are for Natural Gas (.65 Sp. Gr.), and

are based on 1/2" water column pressure drop. Check supply

pressure with a manometer, and local code requirements for

variations. For LPG, reduce pipe diameter one size, but main-

tain a 1/2" minimum diameter. A 'normal' number of Tees and

elbows have been taken into allowance.

Table 6. Natural Gas Pipe Size Requirements*

Gas Supply

Inlet

Tee

Fitting

3 in.

(76mm) Min.

Cap

Nipple

To Equipment

Inlet

Figure 9. Typical design for a sediment trap/drip leg.

Supply Pressure

Minimum

Maximum

Natural Gas

5.5 Inches WC 10.5 Inches WC

(1.3 kPa)

(2.5 kPa)

LP Gas

10.0 Inches WC 13.0 Inches WC

(2.4 kPa)

(3.1 kPa)

Table 5. Gas Supply Pressure Requirements.

This manual is related to the following products: