LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual
Page 34
LAARS Heating Systems
Page 34
TURN GAS ON.
PILOT BURNER LIGHTS?
MAIN VALVE OPENS?
SYSTEM OK
IGNITER WARMS UP
AND GLOWS RED
PILOT VALVE
OPENS
START
• TURN GAS SUPPLY OFF
• SET THERMOSTAT TO
CALL FOR HEAT
SV9501/SV9601 IS
POWERED
(24 VAC NOMINAL)
YES
CHECK:
• LINE VOLTAGE POWER
• LOW VOLTAGE TRANSFORMER
• LIMIT CONTROLLER
• THERMOSTAT
• WIRING
• FAN PROVING SWITCH
ON COMBUSTION AIR BLOWER
UNPLUG IGNITER
MEASURE VOLTAGE AT
TWO BOTTOM TERMINAL OF
SV9501/SV9601
(24 VAC NOMINAL)
YES
YES
YES
YES
YES
NO
NO
NO
YES
NO
NO
NO
Troubleshooting Honeywell SV9501/SV9601
Hot Surface Pilot System (JVH only)
REPLACE IGNITER
REPLACE SV9501/SV9601
MEASURE VOLTAGE TO
SV9501/SV9601.
VOLTAGE MUST BE AT LEAST
19.5 VAC.
REPLACE IGNITER
REPLACE IGNITER SENSOR AND
RETAIN: RESTART TROUBLE-SHOOTING
SEQUENCE. DOES MAIN VALVE OPEN?
DISCARD OLD IGNITER SENSOR
NO
NO
NO
REPLACE
SV9501/
SV9601
CHECK
TRANS-FOR-
MER, LINE
VOLT SUP-
PLY
REPLACE
SV9501/
SV9601.
SAVE OLD
IGNIT-
ER-SENSOR
FOR
SERVICE.