SECTION 8.

Operating Procedures

Before placing the boiler in operation, check and

reset the safety shutoff devices. Once the boiler is

connected to the gas and water piping and after all the

requirements in previous pages have been met, follow

these procedures:

8A. System Start-up

1. Verify that the pump system is operating

properly:

a. Shut off the manual gas valve located

outside the boiler.

b. Raise the wall thermostat high enough to

call for heat.

c. The pump should come on immediately. If

it does not, test the electrical circuits.

2. Pilot and Main Burner Lighting:

a. The JV boiler does not require manual

lighting. The pilot is controlled by the

automatic ignition system.

b. Different models of the JV boiler utilize

various gas valves. Although the gas valves

may have different control knobs, they are

all similar in operation.

c. Understand and follow the operating

instructions that are applicable to the type

of ignition system installed on the boiler.

3. The pilot and main burners will automatically

ignite when there is a call for heat.

8B. Sequence of Operation

1. Wall thermostat will call for heat.

2. Pump relay will turn on the circulating pump.

3. If water temperature is below the limit setting,

the inducer motor relay will turn on the draft

inducer (JVH).

4. Pressure switch will sense the fan (JVH only)

operation and send 24 volts to the flame rollout

switch.

5. In normal conditions, the flame rollout switch

will be in a closed position. 24 volts will be sent

to the gas valve/controller, the igniter will

glow/spark and the pilot valve will open, lighting

the pilot.

6. After pilot is proven to be lit, the main gas valve

will open, the main burners will ignite and

continue until either the primary control, hi-limit

or wall thermostat opens.

7. When the wall thermostat is satisfied, the burners

will shut off. The relays will turn off the draft

inducer (JVH only) and the circulating pump.

When the room temperature falls below the wall

thermostat setting, the cycle will repeat.