beautypg.com

LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual

Page 11

background image

Mini-Therm JV

Page 11

of the pipe, which may cause excessive cooling and

condensation.

3C. Vertical Venting - Category I

(JVS and JVH)

All venting must comply with fuel gas code and

be installed by a licensed professional.

The Mini-Therm JVS or JVH series boiler can

be vented into a masonry chimney, (see Figure 2)

provided several conditions are met:
1. The chimney must have an appropriate tile lining

that is clean, properly constructed and properly

sized.

2. The chimney passage way shall be examined to

ascertain that it is clear and free of obstructions.

WARNING

Do not store any chemical, cleaners, or other

corrosive material near combustion air openings

or in the room. Avoid locating dryer vents in the

vicinity of combustion air openings. Failure to

prevent corrosive materials from mixing with

combustion air can result in reduced boiler life

and unsafe boiler operation.

AVERTISSEMENT

N’entrepposer aucun produit chimique, produit

nettoyant ou produit corrosif à proximité des

bouches d’air de combustion ou dans la pièce.

Éviter de placer des tuyaux de ventilation pour

sécheuse à proximité des bouches d’air de

combustion. Le fait de laisser des maitières

corrosives se mélanger à l’air de combustion

risque de réduire le cycle de vie de l’appareil

de chauffage et de compromettre son

fonctionnement.

3. If a chimney rebuild is required, it shall conform

to nationally recognized standards (see National

Building Code or ANSI/NFPA 211).

4. The boiler must not be connected to a fireplace,

wood stove or other solid fuel burning

equipment.

5. When the boiler and a hot water heater are to be

connected to the same chimney, they must have

their own vent connector and enter the chimney

at least 6” (152mm) apart.

IMPORTANT NOTE: Always provide a minimum

clearance of 6” (152mm) between Type C (single wall)

vent pipe and any combustible materials.

WARNING

Single wall vent pipe must NEVER pass through

interior walls or through floors or ceilings! Failure

to comply with this warning could result in a fire

causing property damage, personal injury, or death!

AVERTISSEMENT

Paroi simple tuyau d'évent doit jamais passer par

l'intérieur les murs ou par planchers ou plafonds

! Le non-respect de cet avertissement peut

provoquer un incendie causant des dommages

matériels ou corporels, ou de mort!

When installing the vent system, all applicable

national and local codes must be followed! The use

of thimbles, firestops and other protective devices,

when penetrating combustible or noncombustible

construction, must be in accordance with all applicable

national and local codes.

Figure 6. Horizontal Vent Termination.

3 (0.9)

MIN.

VENT TERMINAL

VENT TERMINAL

FORCED

AIR INLET

GRADE

SHEET METAL

SCREWS

THIMBLE

ANCHORED

FASTENER

CAULK JOINTS

SEAL ENTIRE

CIRCUMFERENCE

OF JOINT

ANCHORED

FASTENER

CAULK JOINTS

EXHAUST

HOOD

VENT TERMINAL DETAIL

4 (1.2)

MIN.

4 (1.2)

MIN.

12 (3.7)

MIN.

VENT

TERMINAL

6 (1.8) MIN.

LESS THAN

10

(3.0)

Dimensions in

feet (m).

This manual is related to the following products: