beautypg.com

LAARS Mini-Therm JVS (Sizes 50-225) - Install and Operating Manual User Manual

Page 30

background image

LAARS Heating Systems

Page 30

DHW Operation The boiler target for DHW calls

is fixed at 180 deg F.

Note: There is no control of a DHW pump, so the

boiler pump runs with the call for DHW.

Limiting The boiler target is limited to a

minimum and a maximum target to ensure that the

water temperature does not exceed the limits.

1. Target Min - The boiler target minimum is

the point at which the stages will start to turn on to

maintain a minimum water temperature. The Boiler

Minimum water temperature is 130 deg F, regardless

of other calculated targets. To ensure that the water

temperature is greater than the Boiler Minimum water

temperature the target is increased to allow the stages

to cycle on by the Boiler Minimum water temperature,

Boiler Minimum target is set to Boiler Minimum +

differential/2.

2. Target Max - The boiler target maximum is

the point at which the stages will start to turn off to

maintain a maximum water temperature. The Boiler

Maximum water temperature is set by setting dip

switch #4: Boiler Maximum 210°F (Off) / 190°F

(On).

To ensure that the water temperature is less than the

Boiler Maximum water temperature the target is

decreased to allow the stages to cycle off by the Boiler

Maximum water temperature, Boiler Maximum target

is set to Boiler Maximum - differential/2.

Auto Differential The control automatically

adjusts differential to prevent short cycling and

maximize the lifetime of components.

WWSD Operation Warm Weather Shutdown -

WWSD feature is selected via dip switch #3, WWSD

Inactive (Off) / Active 70°F (On). WWSD point is

fixed at 70 deg F. Control exits WWSD when the

outdoor temp falls to 65 F. When there is a call for

HEAT and the control is in WWSD the HEAT call will

be ignored. When there is a call for DHW and the

control is in WWSD the DHW call will be satisfied.

WWSD LED turns on when control detects WWSD.

Summary of Dip Switch Settings:

#1 Two Stage (Off) / Single Stage (On)

(Note: Efficiency may be reduced with 2-stage

operation.)

#2 (Off) / Outdoor Reset (On) (Note: Outdoor Reset

is required for residential operation)

#3 WWSD Inactive (Off) / Active 70°F (On)

#4 Boiler Maximum 210°F (Off) / 190°F (On)

#5 Pump Post Purge Inactive (Off) / Active 3 min.

(On)

LEDs State Description

1. Power

2. Heat – On = call for heat; Flashes for Boiler

sensor error

3. DHW – On = call for DHW; Flashes for

outdoor sensor error

4. WWSD – On = Outdoor Reset AND WWSD

Active AND control in WWSD; Flashes for

outdoor sensor error, operation continues with

fixed boiler target of 140°F.

Summary of Input Sensors:

1. Outdoor sensor - monitors the outside air

temperature for outdoor reset mode

2. Boiler outlet sensor -monitors the water

temperature of the boiler outlet supply

3. System Supply sensor - monitors the water

temperature of the system supply

The boiler outlet sensor is required at all times. If

the boiler outlet sensor has any fault then the control

will flash an error and turns all stages off. The

system supply sensor is optional and utilizes primary

/ secondary piping. If the system supply sensor has

a fault then the control flashes an error message and

operates using the boiler outlet sensor (system supply

= boiler outlet).

JVH050

50

83

JVH075

75

83

JVH100

100

82

JVH125

125

82

JVH160

160

82

JVH225

225

82

JVS050

50

85

JVS075

75

85

JVS100

100

85

JVS125

125

85

JVS160

160

85

JVS225

225

85

106

92

136

118

191

166

43

37

64

56

85

74

102

89

131

114

184

160

41

36

62

54

82

71

MiniTherm Series Boiler Natural Gas

Model

Number

Input, MBH

Heating Capacity,

MBH

Net AHRI Rating

Water, MBH

AFUE, %

Table 10. Efficiencies

This manual is related to the following products: