9B. Electrical Troubleshooting

1. Remove the control box cover on the front of the

boiler.

2. Verify that 115 volts is reaching the boiler by

testing across the black wire and the white wire

on the transformer.

3. Verify 24 volts transformer output by placing

the meter leads on the yellow and red wires. If

24 volts is not evident, replace the transformer.

Perform the following series of tests with one

meter lead attached to the yellow wire on the

transformer.

4. Place the second lead on the “HEAT” connection

on the terminal board. Turn the wall thermostat

high enough to call for heat. If the meter fails to

register 24 volts, the thermostat or its circuit may

be defective.

5. Place the second lead on the purple wire terminal

on the hi-limit switch. If no voltage across the

switch, check for defective hi-limit, open circuit

due to excessive water temperature, or a low

temperature setting.

6. For JVH only, place the second lead on the

blue wire terminal on the fan proving switch. If

voltage is present, skip to step 8. If voltage isn’t

present, connections or the draft inducer/motor

could be defective.

7. Verify the voltage across the roll-out safety

switch.

8. If it is determined that there is voltage to the

gas valve, the pilot is lit and the pilot sensor is

properly positioned, and the thermostat is set

high enough to call for heat, the gas valve or the

pilot assembly may be defective.

9. See Section 8E for LED fault codes on

temperature controller.

Caution

Label all wires prior to disconnection when

servicing controls. Wiring errors can cause

improper and dangerous operation. Verify proper

operation after servicing.

Étiquette

de mise en garde tous les fils avant le

débranchement lors de l'entretien. Les erreurs de

câblage peut causer le mauvais et dangereux.

Vérifier le fonctionnement correct après l'entretien

WARNING

Follow local regulations with respect to installation

of carbon monoxide (CO) detectors and

manufacturer’s maintenance schedule of the

boiler.

AVERTISSEMENT

Conformez-vous aux réglementations locales

pour ce qui est de l'installation de détecteur de

monoxyde de carbone (CO) et du programme de

maintenance du fabricant de la chaudière.