Bacnet pics statement – LAARS M4-LHS - Installation Manual User Manual
Page 47

HT# 059295-00
A
M4-LHS installation and Operation Manual
47
BaCNET PiCS STaTEMENT
Product
Model Number Protocol revision Software Version Firmware Version
M4-LHS BACnet Control
Varies
1.5
2.0
2.0
Vendor
Vendor iD
address and Phone
Laars
Product Description
BACnet Standardized Device Profile (Annex L)
Product
Device Profile
M4-LHS BACnet Control
BACnet Application Specific Controller (B-ASC)
Supported BiBBs (annex k)
Supported BiBBs BiBB Name
DS-RP-B
Data Sharing-ReadProperty-B
DS-WP-B
Data Sharing-WriteProperty-B
DM-DDB-B
Device Management-Dynamic Device Binding-B
DM-DOB-B
Device Management-Dynamic Object Binding-B
DM-DCC-B
Device Management-DeviceCommunicationControl-B
Standard Object Types Supported
Object Type
Creatable Deletable
Analog Value
No
No
Binary Value
No
No
Multi-State Value
No
No
Device
No
No
Data Link Layer Options (annex J)
Product
Data Link
Options
M4-LHS BACnet Control
BACnet MS/TP
Baud Rates: 9600, 19200, 38400
Segmentation Capability
Segmentation Type
Supported
Window Size (MS/TP product limited to 1)
Able to transmit segmented messages
No
Able to receive segmented messages
No
Device address Binding
Product
Static Binding Supported
M4-LHS BACnet Control
No
Character Sets
Product
Character Sets supported
M4-LHS BACnet Control
ANSI X3.4