beautypg.com

System settings, Setback, Purge delay – LAARS M4-LHS - Installation Manual User Manual

Page 31: System run-on, M4-lhs, Alert, A b c d, Hybrid control, 0 min, 10 min

background image

HT# 059295-00

A

M4-LHS installation and Operation Manual

31

SYSTEM SETTiNgS

Button: MENU/

Settings 1 and Settings 2 menus provide access to adjusting and fine-tuning the system for

enhanced comfort and better fuel savings. The M4-LHS behaves differently based on the

selected modes. See "Startup Settings" on page 19.

----- SETTINGS 1 ----

Setback

0

o

F

Purge Delay 1.0min

System Run-On 0min

Lead Rotation Time

BACK ▲ ▼ SELECT

----- SETTINGS 2 ----

Standby Time 10min

Last Stg Hold 0

o

F

BACK ▲ ▼ SELECT

SYSTEM

A
B
C
D

1 2

RUN

PROGRAM

DO NOT APPLY ANY VOLTAGE

TO INPUT TERMINALS

3 4 5 6 7 8 9 10 11 12

13

15

14

17

16

18

20

19

21

24

23

29

25

27

26

28

32

30 31

L N

-

+

+

T

T

O

O

RS-485

mA

GND

VLT

SYS

A

B

C

D

PWR

CUR / VLT

A

-

+

+

mA

GND

VLT

-

+

+

mA

GND

VLT

+

+

mA

22

-

GND

VLT

+

mA

TEMP

OUTDOOR

O

O

TEMP

SYSTEM

EXTENSION

MODULE

CUR / VLT

B

CUR / VLT

C

CUR / VLT

D

PROVE

/DHW

SHUTDOWN

/SETBACK

FOR ALL CIRCUITS

120VAC, 6A RESISTIVE

OUTPUT RATINGS:

1A PILOT DUTY, 15A TOTAL

115VAC 60Hz , 30VA MAX

INPUT RATINGS:

USE COPPER WIRE,

CLASS 1 WIRE ONLY.

CAUTION: RISK OF ELECTRIC SHOCK

More than one disconnect switch may be required

to de-energize the equipment before servicing.

ENCLOSED

ENERGY

MANAGEMENT

EQUIPMENT

99RA

/TSTAT

M4-LHS

HYBRID CONTROL

aLErT

To be able to change the M4-LHS settings the Program/Run Switch must be

set to Program. The switch is located under the Enclosure Wiring Cover for

security. The Enclosure Wiring Cover can be secured using a lock.

Setback

Adjustable from 0F°/0C° to 75F°/42C°

Default: 10F°/6C°

Button: MENU//Setback

• The Setback feature can be used to provide the M4-LHS with a lower temperature Set Point

when less load is required.

• The lower Set Point will appear on the main display indicating this condition.

• For example, if the calculated temperature is 180°F and the Setback is 20°F, then when in

Setback or Night Schedule, the M4-LHS will hold a Set Point of 160°F = 180°F- 20°F. See

"Day - Night Schedule" on page 36.

• A typical use for the Setback is to provide less system temperature to a building during

the Night Schedule or on the weekends when people are asleep or when the building is not

occupied, but heat is still needed.

• The amount of Setback selected is subtracted from the Set Point when a Setback Input

Signal is received or the Night Time schedule setting started.

• If Setback is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/Setback

Mode" on page 24.), the Setback will not be activated unless a Short dry-contact signal is

received on terminals (31 and 32).

• If Shutdown or Tstat is selected as the Shutdown/Tstat/Setback Mode (See "Shutdown/Tstat/

Setback Mode" on page 24.), the Setback will be activated only during the Night Schedule.

------- SETBACK -------

10

o

F

[

]

BACK ▲ ▼ SAVE

aLErT

When using Soft-Off and Last

Stage Hold, the last boiler stage will

not turn off until both parameters

have elapsed. In this case, Soft-Off

will start after the Last Stage Hold.

Purge Delay

Adjustable from 0.0 min to 10.0 min

Default: 1.0 min

Button: MENU//Purge Delay

• Many boilers go through a purge cycle before they are brought on line. When the M4-LHS

activates a boiler, it does not start to calculate its output until the Purge Delay is over. This

allows the boiler to fully come online and begin producing.

• The Purge Delay helps prevent short cycling of any newly activated burner. Once the

burner is activated, it MUST run through the entire Purge Delay period.

• The minimum Purge Delay setting MUST be set to the time required by the boiler

manufacturer. Time entry is in 0.1 of a minute (i.e. 1.5 minute will equal 90 seconds.)

• The Message Display Line will display Purge Delay and the remaining time.

--- PURGE DELAY ---

1.0 min

[

]

BACK ▲ ▼ SAVE

aLErT

Set Purge Delay as per boiler

manufacturer recommendation.

System run-On

Adjustable from 0 min to 360 min

Default: 10 min

Button: MENU//System run-On

• A common use for the System Run-On is to control a system pump in a heating system.

The extra time helps transfer the boiler residual heat to the heating system.

• The System relay will energize whenever the outdoor temperature is below the Outdoor

Cutoff and the Shutdown is Open or the Tstat is closed. When the Outdoor Temperature

rises 2°F above the Outdoor Cutoff or the control is switched to Summer and after the last

burner relay has de-energized, the System relay will remain energized for the System Run-

On period.

-- SYSTEM RUN-ON --

10 min

[

]

BACK ▲ ▼ SAVE