Modulation - outdoor reset - bacnet variable list – LAARS M4-LHS - Installation Manual User Manual
Page 45

HT# 059295-00
A
M4-LHS installation and Operation Manual
45
M
OD
u
La
Ti
ON
- Ou
TDOO
r
rESET
- B
a
C
NET
V
aria
BLE
L
iST
Hybrid
Object ID
Object
Type
Object V
alue
Object Name
Units
Minimum
M
ax
im
um
Definition
Model
Device Object
Read Only
MODEL
Serial Number
Device Object
Read Only
SNUMBER
Version
Device Object
Read Only
VERSION
Operation Mode
100
MUL
TIST
ATE-V
ALUE
Read Only
OPMODE
1
3
1= Hybrid, 2 = Modulation Setpoint, 3 = Modulation Reset
Outdoor
Temperature
200
ANALOG-V
ALUE
Read Only
ODTEMP
Degree F
32000=OPEN,3201=SHOR
T
System
Temperature
300
ANALOG-V
ALUE
Read Only
SYSSEN
Degree F
32000=OPEN,3201=SHOR
T
Control Status
400
MUL
TIST
ATE-V
ALUE
Read Only
CST
AT
1
15
1=SHUTDOWN,2=NO
TST
AT
CALL,3=PROVE F
AILURE,4=
PURGE DLEA
Y,5=W
AITING FOR PROVE,6=SENSOR F
AUL
T,7=
LAG DELA
Y, 8=LAST
ST
AGE HOLD,9=DHW CALL,10 = SYSTEM
RUNON,1
1=SUMMER,12=OUTDOOR CUT
OFF
,13=BOOST
MODE,14=SETBACK MODE,15 = NORMAL
OPERA
TION
Season
500
MUL
TIST
ATE-V
ALUE
Read/W
rite
SEA
1
2
1= Winter
, 2= Summer
Reset Ratio
600
MUL
TIST
ATE-V
ALUE
Read/W
rite
RR
1
11
1 =1.00 OD = 4.00 Sys,2 =1.00 OD = 3.00 Sys,3 =1.00 OD = 2.00 Sys, 4 =1.00 OD = 1.50 Sys,5 =1.00 OD = 1.25 Sys,6 =1.00 OD = 1.00 Sys,,7 =1.25 OD = 1.00 Sys,8 =1.50 OD = 1.00 Sys,9 =2.00 OD = 1.00 Sys,10 =3.00 OD = 1.00 Sys,1
1 = 4.00 OD = 1.00 Sys
Of
fset
700
ANALOG-V
ALUE
Read/W
rite
OFF
Degree F
-50
50
Integer V
alues Only (-1,0,1,2…)
Outdoor Cutof
f
800
ANALOG-V
ALUE
Read/W
rite
CO
Degree F
19
101
Integer V
alues Only (19,20,21…)
Min W
ater
Temp
900
ANALOG-V
ALUE
Read/W
rite
MINW
Degree F
50
180
Integer V
alues Only (50,51,52…)
Max W
ater
Temp
1000
ANALOG-V
ALUE
Read/W
rite
MAXW
Degree F
70
220
Integer V
alues Only (70,71,72…)
Setback
1100
ANALOG-V
ALUE
Read/W
rite
SB
Degree F
0
75
Integer V
alues Only (0,1,2…)
Purge Delay
1200
ANALOG-V
ALUE
Read/W
rite
PDL
Y
Minutes
.1
10
.1 thru .9 after Integer V
alues Only (1,2…)
System Runon
1300
ANALOG-V
ALUE
Read/W
rite
RUNON
Minutes
0
360
Integer V
alues Only (0,1,2…)
Rotation
Time
1400
ANALOG-V
ALUE
Read/W
rite
R
TTIME
Hours
1
1440
Hours since last rotation Integer V
alues Only (1,2,3…)
Standby
Time
1500
ANALOG-V
ALUE
Read/W
rite
STBYDL
Y
Minutes
1
60
Integer V
alues Only (1,2,3…)
Last Stage Hold
1600
ANALOG-V
ALUE
Read/W
rite
LSTHOLD
Degree F
0
30
Integer V
alues Only (0,1,2…)
Gain
1700
MUL
TIST
ATE-V
ALUE
Read/W
rite
GAIN
1
10
Lag Delay
1800
ANALOG-V
ALUE
Read/W
rite
LAGDL
Y
Minutes
0
60
Integer V
alues Only (0,1,2…)
Soft of
f
1900
ANALOG-V
ALUE
Read/W
rite
SOFF
Seconds
0
60
Integer V
alues Only (0,1,2…)
Set
Time
2000
ANALOG-V
ALUE
Read/W
rite
PTIME
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)
Day Schedule
2100
ANALOG-V
ALUE
Read/W
rite
DSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)
Night Schedule
2200
ANALOG-V
ALUE
Read/W
rite
NSCHED
Minutes
1
1440
Time since midnight Integer V
alues Only (1,2,3…)
System Relay
2300
BINAR
Y-V
ALUE
Read Only
SYSRL
Y
False
True
True = Energized, False = De-Engergized
Output Relays
2400 - Max Stages
BINAR
Y-V
ALUE
Read Only
R
Y0 - R
Y Max
Stages
False
True
True = Energized, False = De-Engergized