Modulating operating menu, Alert, 0 min – LAARS M4-LHS - Installation Manual User Manual
Page 29: 10 min

HT# 059295-00
A
M4-LHS installation and Operation Manual
29
aLErT
To be able to change the M4-LHS
settings the Program/Run Switch must
be set to Program. The switch is located
under the Enclosure Wiring Cover for
security. The Enclosure Wiring Cover
can be secured using a lock.
-------- SETTINGS ----
Season
Winter
System Target 140
o
F
BACK ▲ ▼ SELECT
----- SEASON -----
Winter
Summer
BACK ▲ ▼ SAVE
----- SETTINGS 1 ----
Setback
10
o
F
Purge Delay 1.0min
System Run-On 10min
Lead Rotation Time
BACK ▲ ▼ SELECT
------- SETBACK -------
10
o
F
[
]
BACK ▲ ▼ SAVE
--- PURGE DELAY ---
1.0 min
[
]
BACK ▲ ▼ SAVE
-- SYSTEM RUN-ON --
10 min
[
]
BACK ▲ ▼ SAVE
-- LEAD ROTATION --
Manual
Time
Last-On
BACK ▲ ▼ SAVE
----- SETTINGS 2 ----
Standby Time 10min
Last Stg Hold 5
o
F
BACK ▲ ▼ SELECT
-- STANDBY TIME --
10 min
[
]
BACK ▲ ▼ SAVE
LAST STAGE HOLD
5
o
F
[
]
BACK ▲ ▼ SAVE
--- LEAD STAGES ---
Cond Lead
A
Non-Cond Lead
C
BACK ▲ ▼ SAVE
MODULATION SETTINGS
Gain
+0
Lag Delay
0min
Soft-Off Delay 45sec
BACK ▲ ▼ SAVE
DAY/NIGHT SCHEDULE
Set Time
**:**
Day Schedule 6:00a
Night Schedule
8:00p
BACK ▲ ▼ SAVE
OD=
55
o
F SYS=
143
o
F
B
67%
22%
STAGE ◄ ► MENU
- SYSTEM TARGET --
1.00
o
OD = 4.00
o
Sys
1.00
o
OD = 3.00
o
Sys
1.00
o
OD = 2.00
o
Sys
1.00
o
OD = 1.50
o
Sys
1.00
o
OD = 1.25
o
Sys
1.00
o
OD = 1.00
o
Sys
1.25
o
OD = 1.00
o
Sys
1.50
o
OD = 1.00
o
Sys
2.00
o
OD = 1.00
o
Sys
3.00
o
OD = 1.00
o
Sys
4.00
o
OD = 1.00
o
Sys
BACK ▲ ▼ SAVE
------- OFFSET ------
+0
o
F
[
]
BACK ▲ ▼ SAVE
- OUTDOOR CUTOFF -
65
o
F
[
]
BACK ▲ ▼ SAVE
MINIMUM WATER TEMP
70
o
F
[
]
BACK ▲ ▼ SAVE
MAXIMUM WATER TEMP
200
o
F
[
]
BACK ▲ ▼ SAVE
reset
----- SET POINT -----
0
o
F
[
]
BACK ▲ ▼ SAVE
- OUTDOOR CUTOFF -
65
o
F
[
]
BACK ▲ ▼ SAVE
Set Point
MODuLaTiNg OPEraTiNg MENu