Table 11 — Field Wiring for Incoming Conductors

Sized for 125% of Heater Load

LEGEND

*Values are based on Table 310-16 of the NEC (National Electrical

Code) for 75 C insulated copper wire. Not more than 3 conductors
in a raceway.

NOTES:

1. Be sure to consider length of wiring run and possible voltage

drops when sizing wires.

2. Field power wiring — Heaters are furnished with a terminal

block sized for incoming copper conductors with 75 C insulation
rated to carry at least 125% of the heater load. However, con-
ductors can be sized to carry 100% of the heater load if the
heater is rated at 50 kW or more, and the heater is controlled by
a cycling device such as a multi-stage thermostat, step control-
ler, or SCR (silicon control rectifier) power controller. Terminal
blocks and knockouts are sized to handle either 100% or 125%
conductors.

Discharge Modification —

If field modification of

discharge position is required, 39L fans can be converted (by a

skilled mechanic) to any standard hand and discharge without

any additional parts. (NOTE: This does not apply to a model

change conversion.) All mounting holes are prepunched.

To convert a 39L fan, note the following:

1. Sizes 03-18 without inlet guide vanes (IGVs) — See

Fig. 33. It is not necessary to remove the bearing support

channels from the fan housing.
Sizes 21 and 25 without IGV and 06-25 with IGVs —

See Fig. 34. The “A” frame support must be removed. To

change from upblast to horizontal discharge or from

horizontal to upblast discharge, the bearings must be

relocated to keep the wheel centered in the housing. To

change from upblast front (UBF) to upblast rear (UBR)

or from top horizontal front (THF) to top horizontal rear

(THR) or vice versa, turn the entire fan housing 180 de-

grees about its base.

2. Inlet guide vane actuators and linkages, where provided,

may be moved to the opposite fan scroll side sheet.
NOTE: The swivel joint must be at the 12 o’clock posi-

tion on the IGV assembly. (See Fig. 12.) The jackshaft

crankarm, attached to the jackshaft at the “A” frame, will

sit vertically up on all units. Figure 12 illustrates a jack-

shaft crankarm in the vertical up position.

3. The fan shaft may be driven out and reinstalled to place

the drive pulley on the opposite end.

4. The fan scroll is prepunched for horizontal or vertical dis-

charge to match the support angles at the base of the unit.

5. The motor and motor base may be rotated to place the

motor at the front or rear of the unit. Proper location is

that which results in the longest drive center line distance.

The motor conduit box location may need to be reversed.

6. When hand of fan is changed, it may be necessary to turn

the discharge panel inside-out to fit correctly with the fan

discharge. In this case, remove the existing insulation and

install new duct-liner type insulation on the opposite side

of the discharge panel.

7. Rebalancing of the unit is recommended.

WIRE SIZE

(AWG or kcmil)

LOAD AMPS*

WIRE SIZE

(AWG or kcmil)

LOAD AMPS*

Copper

Copper

12

16

1/0

120

10

24

2/0

140

8

40

3/0

160

6

52

4/0

184

4

68

250

204

3

80

300

228

2

92

350

248

1

104

400

268

500

304

AWG

American Wire Gage

kcmil — Thousand Circular Mils

Fig. 33 — Fan Discharge Positions, Fans without IGVs

LEGEND

THF

Top Horizontal Front

THR — Top Horizontal Rear
UBF — Upblast Front
UBR — Upblast Rear