beautypg.com

Table 5 — chilled water coil circuiting data, Fig. 23 — typical direct-expansion row split coil – Carrier 39LB User Manual

Page 17

background image

17

Refrigerant Piping, Direct-Expansion (DX)
Coils (Fig. 23) —

Direct-expansion coils are divided into

2 or 4 splits depending upon the unit size and coil circuiting.

See Table 7 for coil circuiting data. Each split requires its own

distributor nozzle, expansion valve, and suction piping. Suction

connections are on the air entering side when the coil is proper-

ly installed. Matching distributor connections for each coil split

are on the air leaving side. See unit label or certified drawing to

assure connection to matching suction and liquid connections.

See Table 8 for distributor part numbers.

Table 4 — Hot Water Coil Circuiting Data

LEGEND

NOTE: All hot water coils have 1

1

/

2

-in. MPT.

Table 5 — Chilled Water Coil Circuiting Data

LEGEND

NOTES:

1. Connection sizes are MPT — inches.
2. Sizes 21-25 have 2 coils.

Direct-expansion coils are shipped pressurized with dry

air. Release pressure from each coil split through valves in

protective caps before removing caps.

Do not leave piping open to the atmosphere unnecessar-

ily. Water and water vapor are detrimental to the refrigerant

system. Until the piping is complete, recap the system and

charge with nitrogen at the end of each workday. Clean all

piping connections before soldering joints.

The lower split of face split coils should be first on, last

off.

Row split coils utilize special intertwined circuits (as

shown in Fig. 23); either split of these row split coils can be

first on, last off.

39L UNIT SIZE

03

06

08

10

12

15

18

21

25

No. of Circuits

1-ROW H

6

8

10

10

10

13

15

15

13

2-ROW H

F

6

8

10

10

10

13

15

15

13

12

16

20

20

20

26

30

30

36

F

Full Circuit

H

Half Circuit

LARGE FACE AREA (39LA, 39LD)

COIL

TYPE

CIRCUIT

UNIT SIZE

03

06

08

10

12

Face Area (sq ft)

3.63

5.90

7.90

9.54

11.18

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

4-ROW

Q

4

1

1

/

2

5

1

1

/

2

H

8

1

1

/

2

10

1

1

/

2

12

1

1

/

2

12

1

1

/

2

12

1

1

/

2

F

16

1

1

/

2

20

1

1

/

2

24

2

1

/

2

24

2

1

/

2

24

2

1

/

2

D

6-ROW

H

8

1

1

/

2

10

1

1

/

2

12

1

1

/

2

12

1

1

/

2

12

1

1

/

2

F

16

1

1

/

2

20

1

1

/

2

24

2

1

/

2

24

2

1

/

2

24

2

1

/

2

D

36

2

1

/

2

36

2

1

/

2

36

2

1

/

2

LARGE FACE AREA (39LA, 39LD)

COIL

TYPE

CIRCUIT

UNIT SIZE

15

18

21

25

Face Area (sq ft)

14.91

17.71

21.60

25.00

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

No.

Circuits

Connection

Size

4-ROW

Q

H

16

1

1

/

2

19

1

1

/

2

19

1

1

/

2

22

1

1

/

2

F

32

2

1

/

2

38

2

1

/

2

38

2

1

/

2

44

2

1

/

2

D

76

2

1

/

2

88

2

1

/

2

6-ROW

H

16

1

1

/

2

19

1

1

/

2

19

1

1

/

2

F

32

2

1

/

2

38

2

1

/

2

38

2

1

/

2

44

2

1

/

2

D

48

2

1

/

2

57

2

1

/

2

57

2

1

/

2

66

2

1

/

2

D

Double Circuit

F

Full Circuit

H

Half Circuit

Q

Quarter Circuit

Fig. 23 — Typical Direct-Expansion

Row Split Coil

This manual is related to the following products: