EVCO EC3563 User Manual
Page 3
3
EC 3-563E 3/95
CODE PARAMETER
DESCRIPTION
MIN
MAX
U.M. STANDARD
/
PROBE
/0
kind of probe
30 = 4-20 mA ; 31 = 0-20 mA
30
31
----
30
/1
calibration
-9.0
+10
bar
0
/2
digital filter(speed response) 0=0s; 1=0.4s; 2=1.2s; 3=3.0s; 4=8.0s; 5=19.8s; 6=48.0s
0
6
——
3
/4
without leading zeros
0=NO; 1=SI
0
1
——
1
/5
with decimal point
0=NO; 1=SI
0
1
----
0
/6
start of scale for input 0-20 mA or 4-20 mA corrispondent to input's minimum value
-99
999
bar
see table
/7
end of scale for input 0-20 mA or 4-20 mA corrispondent to input's maximum value
-99
999
bar
see table
L
NETWORK CONNECTION
L1
instrument address
1
15
——
1
L2
instrument group
0
7
----
0
CONFIGURATION PARAMETERS
HOW TO ENTER THE CONFIGURATION KEY
Use a suitable tool (for instance, a small top screw-driver) to operate on the key though the side openings.
notes
N.B. On request, it is possible to configure the instrument with different unit of measure.
The transducers pressure ranges are to be considered as " relative to atmospheric pressure ";
the unit of measure is bar (1 bar = 0.1 MPa; 1 MPa = 10 bar).
TABLE
connected
range
parameter /6
parameter /7
transducer
(bar)
(bar)
(bar)
EC PRS 00
-0.5÷7
-0.5
7
EC PRS 01
0÷25
0
25
EC PRS 02
0÷30
0
30
EC PRS 03
0÷250
0
250
CUSTOM
configurable according to the needs