EC 3-563E 3/95

CODE PARAMETER

DESCRIPTION

MIN

MAX

U.M. STANDARD

/

PROBE

/0

kind of probe

30 = 4-20 mA ; 31 = 0-20 mA

30

31

----

30

/1

calibration

-9.0

+10

bar

0

/2

digital filter(speed response) 0=0s; 1=0.4s; 2=1.2s; 3=3.0s; 4=8.0s; 5=19.8s; 6=48.0s

0

6

——

3

/4

without leading zeros

0=NO; 1=SI

0

1

——

1

/5

with decimal point

0=NO; 1=SI

0

1

----

0

/6

start of scale for input 0-20 mA or 4-20 mA corrispondent to input's minimum value

-99

999

bar

see table

/7

end of scale for input 0-20 mA or 4-20 mA corrispondent to input's maximum value

-99

999

bar

see table

L

NETWORK CONNECTION

L1

instrument address

1

15

——

1

L2

instrument group

0

7

----

0

CONFIGURATION PARAMETERS

HOW TO ENTER THE CONFIGURATION KEY

Use a suitable tool (for instance, a small top screw-driver) to operate on the key though the side openings.

notes

N.B. On request, it is possible to configure the instrument with different unit of measure.

The transducers pressure ranges are to be considered as " relative to atmospheric pressure ";

the unit of measure is bar (1 bar = 0.1 MPa; 1 MPa = 10 bar).

TABLE

connected

range

parameter /6

parameter /7

transducer

(bar)

(bar)

(bar)

EC PRS 00

-0.5÷7

-0.5

7

EC PRS 01

0÷25

0

25

EC PRS 02

0÷30

0

30

EC PRS 03

0÷250

0

250

CUSTOM

configurable according to the needs