Activating the multifunction digital input the instrument interacts on the outputs activity ac-

cording what established with the parameters of the family i.

WORKING SETPOINT

WORKING SETPOINT SETTING (WORKING TEMPERATURE)
To modify the working setpoint value keep pushed the key T3 (the instrument displays the

actual value) and at the same time push and release over and over the key T1 or T2 as long as

the instrument displays the desired value (keeping pushed the key T1 or T2 the value gets

decreased or increased more quickly): after the modification release the key T3 last; during the

pressure of the key T3 the LED L1 flashes quickly to indicate that a working setpoint setting

procedure is running (to the release of the key T3 the instrument automatically turns out from

the working setpoint setting procedure).
ADDITIONAL INFORMATIONS
-

for the whole period of a corrupted memory data alarm the access to the working

setpoint setting procedure is refused

-

the working setpoint is programmable within the limits established with the param-

eters r 1 and r 2

-

if the parameter r 5 has value 1 the working setpoint can not be modified as long as

the parameter r 5 gets set to 0

-

the working setpoint value gets stored in a non volatile memory even if a lack of

power supply happens.

WORKING SETPOINT
LABEL MIN. MAX. U.M. ST.

WORKING SETPOINT

r 1

r 2

(*)

0.0

working setpoint

It establishes the temperature associated to the compressor output.

CONFIGURATION PARAMETERS

CONFIGURATION PARAMETERS SETTING
Configuration parameters are arranged on two levels, to protect the most tricky settings against

undesirable violations and they are arranged in families that can be recognized through the

initial letter of the label.
To gain access to the first level keep pushed at the same time for four seconds at least the keys

T1 and T2 (passed four seconds the instrument displays the label PA).
To select a parameter of the first level push and release over and over the key T1 or T2 as long

as the instrument displays the label of the desired parameter.
To modify the parameter value keep pushed the key T3 (the instrument displays the actual

value) and at the same time push and release over and over the key T1 or T2 as long as the

instrument displays the desired value (keeping pushed the key T1 or T2 the value gets de-

creased or increased more quickly); after the modification release the key T3 last (to the

release of the key T3 the instrument displays the label of the parameter again).
To gain access to the second level enter inside the first level and select the label PA.
Keep pushed the key T3 (the instrument displays the actual value) and at the same time push

and release over and over the key T1 or T2 as long as the instrument displays -19 (keeping

pushed the key T1 or T2 the value gets decreased or increased more quickly): after the modi-

fication release the key T3 last (to the release of the key T3 the instrument displays the label PA

again); keep pushed at the same time for four seconds at least the keys T1 and T2 (passed four

seconds the instrument displays the first parameter of the second level).
To select a parameter of the second level push and release over and over the key T1 or T2 as

long as the instrument displays the label of the desired parameter.
To modify the parameter value keep pushed the key T3 (the instrument displays the actual

value) and at the same time push and release over and over the key T1 or T2 as long as the

instrument displays the desired value (keeping pushed the key T1 or T2 the value gets de-

creased or increased more quickly); after the modification release the key T3 last (to the

release of the key T3 the instrument displays the label of the parameter again).
To turn out from the configuration parameters setting procedure keep pushed at the same time

for four seconds at least the keys T1 and T2 or do not operate with the keys for fifty seconds

at least (time-out exit).
ADDITIONAL INFORMATIONS
-

for the whole period of a corrupted memory data alarm the access to the configura-

tion parameters setting procedure is refused

-

the modification of the parameter /Ab value has not immediate effect; to obtain this

effect, after the modification turn OFF and turn ON again the instrument

-

the modification of a parameter value which unit of measure is the hour or the

minute or the second has not immediate effect; to obtain this effect it must not be

executed during the course of the value

-

the configuration parameters values get stored in a non volatile memory even if a

lack of power supply happens.

CONFIGURATION PARAMETERS
LABEL MIN. MAX. U.M. ST.

PASSWORD

PA

-55

99

---

0

password (§)

It is the password that permits to gain access to the second level.
LABEL MIN. MAX. U.M. ST.

MEASURE INPUTS

/ 0

1

3

---

1

kind of probe

It establishes the kind of probe that the instrument must recognize to its measure inputs, as

indicated:

1 =

PTC probe

3 =

NTC probe.

/1A

-10

+10.0 (*)

0.0

cabinet probe calibration (§)

It establishes a threshold to add algebraically to the signal coming from the cabinet probe (for

instance to correct the signal).
/1b

-10

+10.0 (*)

0.0

evaporator probe calibration (§)

It is significant exclusively if the parameter /Ab has value 1, it establishes a threshold to add

algebraically to the signal coming from the evaporator probe (for instance to correct the sig-

nal).

To display the temperature read by the evaporator probe see the chapter ADDITIONAL FUNC-

TIONS.
/ 5

0

1

---

1

decimal point

It is significant exclusively if the parameter / 8 has value 1, it establishes the resolution with

which the temperature gets displayed, as indicated:

0 =

the temperature gets displayed with the resolution of the unit of measure

1 =

the temperature gets displayed with the resolution of 1/10 of the unit of measure.

/ 8

0

1

---

1

unit of measure

It establishes the unit of measure with which the temperature gets displayed, as indicated:

0 =

the unit of measure is the Fahrenheit degree

1 =

the unit of measure is the Celsius degree.

/Ab

0

1

---

1

evaporator probe enabling

It establishes if to enable the evaporator probe, as indicated:

0 =

the evaporator probe is disabled

1 =

the evaporator probe is enabled.

LABEL MIN. MAX. U.M. ST.

ON-OFF TEMPERATURE REGULATOR ASSOCIATED TO THE

WORKING SETPOINT AND TO THE COMPRESSOR OUT-

PUT

r 0

+0.1 +15.0 (*)

+2.0 hysteresis (differential) (§)

It establishes the hysteresis (differential) relative to the working setpoint and to the setpoint

established with the parameter r 8.
r 1

-99

+99.9 (*)

-50

minimum working setpoint programmable

It establishes the minimum working setpoint programmable; the instrument automatically veri-

fies if the value established with the parameter r 1 is below the maximum working setpoint

programmable established with the parameter r 2.
r 2

-99

+99.9 (*)

+50.0 maximum working setpoint programmable

It establishes the maximum working setpoint programmable; the instrument automatically

verifies if the value established with the parameter r 2 is above the minimum working setpoint

programmable established with the parameter r 1.
r 5

0

1

---

0

locking of the working setpoint modification

It establishes if to prevent the modification of the working setpoint, as indicated:

0 =

the working setpoint can be modified

1 =

the working setpoint can not be modified as long as the parameter r 5 gets set to 0.

r 8

-99

+99.9 (*)

0.0

auxiliary working setpoint

It is significant exclusively if the parameter i 0 has value 6 or 7 or if the parameter Hr2 has

values different to 0.0, it establishes the temperature associated to the compressor output

during a multifunction digital input activation and during an Energy Saving cycle.
LABELMIN. MAX. U.M. ST.

COMPRESSOR OUTPUT PROTECTION

C 0

0

240 min. 0

disabling time to the output activation from the instru-

ment start

It establishes the time that disables the output activation from the moment of the instrument

start.
C 1

0

240 min. 5

disabling time to the output activation from the previ-

ous activation

It establishes the time that disables the output activation from the moment of the previous

output activation.
C 2

0

240 min. 3

disabling time to the output activation from the previ-

ous deactivation

It establishes the time that disables the output activation from the moment of the previous

output deactivation.
C 4

0

1

---

0

disabling time to the output activation and deactivation

It establishes if to disable the output activation and deactivation for a fixed time, as indicated:

0 =

inactive

1 =

the output activation and deactivation get disabled for 3 sec.

C 5

1

240 min. 10

cycle time for the output activation during a cabinet

probe failure alarm

It establishes the cycle time for the output activation due to the contribution of the percentage

established with the parameter C 6 during a cabinet probe failure alarm.
C 6

0

100 %

50

percentage of the cycle time during which the output

gets activated during a cabinet probe failure alarm

It establishes the percentage of the cycle time established with the parameter C 5 during which

the output must remain continuously activated in the course of the cycle time during a cabinet

probe failure alarm, except what established with the disabling times to the compressor output

activation.
LABELMIN. MAX. U.M. ST.

DEFROST REGULATOR

d 0

0

99

hours 8

defrost interval

It is significant exclusively if the parameter d E has values different to 3.
If the parameter d E has value 0 it establishes the time interval that pass from the moment of the

instrument start or from the moment in which the instrument presents a request of a defrost

cycle to the moment in which the instrument automatically presents the following request of a

defrost cycle.
If the parameter d E has value 1 it establishes for which time interval the compressor output

must be remained activated from the moment of the instrument start or from the moment in

which the instrument activates a defrost cycle in order that the instrument can automatically

activate the following defrost cycle.
If the parameter d E has value 2 it establishes for which time interval the temperature read by

the evaporator probe must be remained below the setpoint established with the parameter d F

from the moment of the instrument start or from the moment of a defrost cycle end in order

that the instrument can automatically present the following request of a defrost cycle.
If the parameter d 0 has value 0 the instrument never automatically presents a request of a

defrost cycle, except what established with the parameter d 4.
d 1

0

1

---

1

kind of defrost

It establishes the kind of defrost that the instrument must manage, as indicated:

0 =

to resistances (electrical)

1 =

to hot gas (reversal of cycle).