Configurability, How to order, Signals and alarms – EVCO EC3T30 User Manual
Page 2: Technical da
![background image](/manuals/675493/2/background.png)
To gain access to the second level enter inside the first level and select the label PA.
Keep pushed the key T3 (the instrument displays the actual value) and at the same time push
and release over and over the key T1 or T2 as long as the instrument displays -19 (keeping
pushed the key T1 or T2 the value gets decreased or increased more quickly): after the modi-
fication release the key T3 last (to the release of the key T3 the instrument displays the label PA
again); keep pushed at the same time for four seconds at least the keys T1 and T2 (passed four
seconds the instrument displays the first parameter of the second level).
To select a parameter of the second level push and release over and over the key T1 or T2 as
long as the instrument displays the label of the desired parameter.
To modify the parameter value keep pushed the key T3 (the instrument displays the actual
value) and at the same time push and release over and over the key T1 or T2 as long as the
instrument displays the desired value (keeping pushed the key T1 or T2 the value gets de-
creased or increased more quickly); after the modification release the key T3 last (to the
release of the key T3 the instrument displays the label of the parameter again).
To turn out from the configuration parameters setting procedure keep pushed at the same time
for four seconds at least the keys T1 and T2 or do not operate with the keys for fifty seconds
at least (time-out exit).
ADDITIONAL INFORMATIONS
-
for the whole period of a corrupted memory data alarm the access to the configura-
tion parameters setting procedure is refused
-
the modification of a parameter value which unit of measure is the hour or the
minute or the second has not immediate effect; to obtain this effect it must not be
executed during the course of the value
-
the configuration parameters values get stored in a non volatile memory even if a
lack of power supply happens.
CONFIGURABILITY
CONFIGURABILITY
CONFIGURABILITY
CONFIGURABILITY
CONFIGURABILITY
WORKING SETPOINT
LABEL MIN. MAX. U.M. ST.
WORKING SETPOINT
r1
r2
(*)
0
working setpoint
It establishes the temperature associated to the output K 1.
CONFIGURATION PARAMETERS
LABEL MIN. MAX. U.M. ST.
PASSWORD
PA
-55
99
---
0
password (§)
It is the password that permits to gain access to the second level.
LABEL MIN. MAX. U.M. ST.
MEASURE INPUT
/0
1
3
---
1
kind of probe
It establishes the kind of probe that the instrument must recognize to its measure input, as
indicated:
1 =
PTC probe
3 =
NTC probe.
/1
-55
+99
(*)/8 0
calibration (§)
It establishes a threshold to add algebraically to the signal coming from the measure input (for
instance to correct the signal).
/2
0
6
---
3
digital filter
It establishes a time constant to apply to the signal coming from the measure input, as indi-
cated:
0 =
0 sec.
1 =
0.4 sec.
2 =
1.2 sec.
3 =
3.0 sec.
4 =
8.0 sec.
5 =
19.8 sec.
6 =
48.0 sec.
/8
0
1
---
1
unit of measure
It establishes the unit of measure with which the temperature gets displayed, as indicated:
0 =
the unit of measure is the Fahrenheit degree
1 =
the unit of measure is the Celsius degree.
LABELMIN. MAX. U.M. ST.
ON-OFF TEMPERATURE REGULATOR ASSOCIATED TO
THE WORKING SETPOINT AND TO THE OUTPUT K 1
r0
-15
+15 (*)
+2
hysteresis (differential) (§)
It establishes the hysteresis (differential) relative to the working setpoint.
r1
-55
+99
(*)
-55
minimum working setpoint programmable
It establishes the minimum working setpoint programmable; the instrument automatically veri-
fies if the value established with the parameter r1 is below the maximum working setpoint
programmable established with the parameter r2.
r2
-55
+99
(*)
+99
maximum working setpoint programmable
It establishes the maximum working setpoint programmable; the instrument automatically
verifies if the value established with the parameter r2 is above the minimum working setpoint
programmable established with the parameter r1.
r3
0
1
---
0
cooling or heating functioning
It establishes the output functioning, as indicated:
0 =
cooling functioning
1 =
heating functioning.
LABEL MIN. MAX. U.M. ST.
OUTPUT K 1 PROTECTION
C0
0
15
min. 0
disabling time to the output activation from the instru-
ment start
It establishes the time that disables the output activation from the moment of the instrument
start.
C1
0
15
min. 0
disabling time to the output activation from the previous
activation
It establishes the time that disables the output activation from the moment of the previous
output activation.
C2
0
15
min. 0
disabling time to the output activation from the previous
deactivation
It establishes the time that disables the output activation from the moment of the previous
output deactivation.
Working range:
from -50 to +99
°
C (-58 to +99
°
F) for PTC probe, from
-40 to +99
°
C (-40 to +99
°
F) for NTC probe.
Setting range:
from -55 to +99
°
C (-55 to +99
°
F).
Resolution:
1
°
F with unit of measure in Fahrenheit, 1
°
C with unit of
measure in Celsius.
Display:
2-digit display 12.5 mm (0.49 in.) high red LED display
with automatic minus sign, output status indicator.
Outputs:
one change-over contact 8 (3) A @ 250 Vac relay for regu-
lation load management.
Serial port:
TTL with EVCOBUS protocol communication, for the con-
nection to the CLONE configurer/cloner and RICS supervi-
sion systems.
HOW TO ORDER
HOW TO ORDER
HOW TO ORDER
HOW TO ORDER
HOW TO ORDER
CODING SYSTEM
Instrument name:
EC 3-T30.
Desired measure input:
P (for PTC/NTC probes).
Desired power supply:
220 (230 Vac)
115 (115 Vac).
Options:
custom configuration.
2
3
C3
0
1
---
0
output status during a probe failure alarm
It establishes the status to which the output gets forced during a probe failure alarm, as indi-
cated:
0 =
during a probe failure alarm the output gets forced to the status OFF
1 =
during a probe failure alarm the output gets forced to the status ON.
C4
0
1
---
0
disabling time to the output activation and deactivation
It establishes if to disable the output activation and deactivation for a fixed time, as indicated:
0 =
inactive
1 =
the output activation and deactivation get disabled for 3 sec.
LABEL MIN. MAX. U.M. ST.
TEMPERATURE ALARM REGULATOR
A0
+1
+15
(*)
+2
hysteresis (differential)
It establishes the hysteresis (differential) relative to the parameters A1 and A2.
A1
-55
0
(*)
0
lower alarm set relative to the working setpoint
It establishes a threshold to add algebraically to the working setpoint; the value so obtained
establishes the temperature below which the lower temperature alarm gets activated.
If the parameter A1 has value 0 the lower temperature alarm never gets activated.
A2
0
+99
(*)
0
upper alarm set relative to the working setpoint
It establishes a threshold to add algebraically to the working setpoint; the value so obtained
establishes the temperature above which the upper temperature alarm gets activated.
If the parameter A2 has value 0 the upper temperature alarm never gets activated.
A3
0
15
hours 0
disabling time to the alarm activation from the instru-
ment start
It establishes the time that disables the temperature alarm activation from the moment of the
instrument start.
LABEL MIN. MAX. U.M. ST.
CONNECTION IN A SERIAL NETWORK WITH EVCOBUS
PROTOCOL COMMUNICATION
L1
1
15
---
1
instrument address
It establishes the address to which the instrument (slave) answers when it is connected to a
serial network with EVCOBUS protocol communication managed from a master (for instance a
Personal Computer).
L2
0
7
---
0
instrument group
It establishes the group to which the instrument (slave) answers when it is connected to a
serial network with EVCOBUS protocol communication managed from a master (for instance a
Personal Computer).
ADDITIONAL INFORMATIONS
-
the symbol (§) indicates that the parameter is of the first level
-
the symbol (*) indicates that the unit of measure depends from the parameter /8.
SIGNALS AND ALARMS
SIGNALS AND ALARMS
SIGNALS AND ALARMS
SIGNALS AND ALARMS
SIGNALS AND ALARMS
SIGNALS
If the LED L1 is turned ON it means that the output K 1 is activated.
If the LED L1 flashes it means that a count of a disabling time to the output K 1 activation is
running (see the parameters C0, C1, C2 and C4).
ALARMS
If the instrument displays the indication E2 flashing and the buzzer utters an intermittent
beep (corrupted memory data alarm) it means that there is a corruption of the configuration
data in the memory (turn OFF and turn ON again the instrument: if to the turning ON again the
alarm does not disappear the instrument must be replaced); during this alarm the access to
the working setpoint setting and the configuration parameters setting procedures is refused
and the output K 1 gets forced to the status OFF.
If the instrument displays the indication E0 flashing and the buzzer utters an intermittent
beep (probe failure alarm) it means that: the kind of connected probe is not proper (see the
parameter /0), the probe is faulty (verify the probe integrity), there is a mistake in the instru-
ment-probe connection (verify the instrument-probe connection integrity), the temperature
read by the probe is outside the limits permitted by the probe in use (verify that the tempera-
ture near the probe be inside the limits permitted by the probe); during this alarm the output
K 1 gets forced to the status established with the parameter C3.
If the instrument displays the temperature read by the probe flashing and the buzzer utters an
intermittent beep (temperature alarm) it means that the temperature read by the probe is
outside the limit established with the parameter A1 or A2 (see the parameters A0, A1 and A2);
inactive.
If the instrument displays the indication 99 flashing (end of scale display) it means that the
temperature read by the probe is outside the working range permitted by the instrument (verify
that the temperature near the probe be inside the limits permitted by the instrument); inactive.
ADDITIONAL INFORMATIONS
-
the alarm codes are related in order of precedence.
TECHNICAL DA
TECHNICAL DA
TECHNICAL DA
TECHNICAL DA
TECHNICAL DAT
T
T
T
TA
A
A
A
A
TECHNICAL DATA
Case:
plastic black (PC-ABS), self-extinguishing.
Size:
74 x 32 x 65 mm (2.91 x 1.25 x 2.55 in.).
Installation:
panel mounting, panel cutout 71 x 29 mm (2.79 x 1.14 in.),
with the equipped screw or spring brackets.
Type of protection:
IP 54.
Connections:
screw terminal blocks with pitch 5 mm (0.19 in., power
supply, measure input and output) for cables up to 2.5 mm²
(0.38 in.²), five poles single line male connector with pitch
5.08 mm (0.2 in., serial port).
Ambient temperature:
from 0 to +60
°
C (+32 to +140
°
F, 10 ... 90 % of not con-
densing relative humidity).
Power supply:
230 Vac or 115 Vac, 50/60 Hz, 1 VA.
Insulation class:
II.
Alarm buzzer:
incorporated.
Measure inputs:
1 configurable for PTC/NTC probes.