beautypg.com

EVCO EVF215N9 User Manual

Page 5

background image

Evco S.p.A. • Code 104F215E00 • page 5/8

12

WORK SET-POINT AND CONFIGURATION PARAMETERS

12.1

Work set-point

MIN.

MAX. U. M.

DEF.

r1

r2

°C/°F (1)

-18.0

12.2

Configuration parameters

DEF.

MIN.

MAX. U. M.

PAR.

SP

r1

r2

°C/°F (1)

-18.0

DEF.

MIN.

MAX. U. M.

PAR.

CA1

-25.0 25.0

°C/°F (1)

0.0

CA2

-25.0 25.0

°C/°F (1)

0.0

CA3

-25.0 25.0

°C/°F (1)

0.0

P1

0

1

- - - -

1

P2

0

1

- - - -

0

P3

0

2

- - - -

1

P4

0

1

- - - -

1

P8

0

250

ds

5

P9

0

2

- - - -

1

DEF.

MIN.

MAX. U. M.

PAR.

r0

0.1

15.0

°C/°F (1)

2.0

r1

-99.0 r2

°C/°F (1)

-50.0

r2

r1

99.0

°C/°F (1)

50.0

r3

0

1

- - - -

0

r4

0.0

99.0

°C/°F (1)

0.0

r5

0.0

99.0

°C/°F (1)

0.0

r6

0

240

min

30

r7

0.0

99.0

°C/°F (1)

10.0

DEF.

MIN.

MAX. U. M.

PAR.

C0

0

240

min

0

C1

0

240

min

5

C2

0

240

min

3

C3

0

240

s

0

C4

0

240

min

10

C5

0

240

min

10

C6

0.0

199.0 °C/°F (1)

80.0

C7

0.0

199.0 °C/°F (1)

90.0

C8

0

15

min

1

C10

0

9999 h

0

DEF.

MIN.

MAX. U. M.

PAR.

d0

0

99

h

8

d1

0

2

- - - -

0

d2

-99.0 99.0

°C/°F (1)

2.0

d3

0

99

min

30

d4

0

1

- - - -

0

d5

0

99

min

0

d6

0

1

- - - -

1

d7

0

15

min

2

d8

0

4

- - - -

0

d9

-99.0 99.0

°C/°F (1)

0.0

d11

0

1

- - - -

0

d15

0

99

min

0

d16

0

99

min

0

d17

1

10

- - - -

1

d18

0

3,000 min

40

d19

0.0

40.0

°C/°F (1)

3.0

WORK SET-POINT
work set-point; see also r0

WORK SET-POINT
work set-point; see also r0
MEASUREMENT INPUTS
cabinet probe offset
evaporator probe offset
condenser probe offset
degree Celsius decimal point (for the sizes displayed during normal functioning)
1 = YES
temperature unit of measurement (2)
0 = °C
1 = °F
evaporator probe function
0 = no probe
1 = defrosting probe and probe for the temperature control system of the evaporator fan
2 = probe for the temperature control system of the evaporator fan
enabling of the condenser probe
1 = YES
display delay of the temperature variation detected by the probes
type of backlight
0 = off during the on status and active keys with low light intensity
1 = with low light intensity during the on state and active keys with high light intensity
2 = with high light intensity during the on state and all keys with high light intensity
MAIN REGULATOR
work set-point differential
minimum work set-point
maximum work set-point
block of work set-point modification (with the procedure indicated in paragraph 5.2)
1 = YES
temperature increases during Energy Saving function; see also i5, i10, HE1 and HE2
temperature decrease during Overcooling function; see also r6
duration of the Overcooling function; see also r5
minimum “cabinet temperature - work set-point” difference (on instrument switch-on) such to cause the exclusion of the consequent evaporator temperature value from those
used for the calculation of the relative average (for the activation of defrosting; only if d8 = 3); see also d17 (3)
COMPRESSOR PROTECTIONS
compressor switch-on delay from instrument switch-on (3)
minimum time between two consecutive switch-ons of the compressor; also pressure switch-on delay from the conclusion of the cabinet probe error (“Pr1”code) (4) (5)
minimum duration of compressor switch-off (4)
minimum duration of compressor switch-on
compressor switch-off duration during cabinet probe error (“Pr1” code); see also C5
compressor switch-on duration during cabinet probe error (“Pr1” code); see also C4
condenser temperature over which the overheated condenser alarm is activated (“COH” code) (6)
condenser temperature over which the compressor blocked alarm is activated (“CSd” code)
compressor blocked alarm delay (“CSd” code) (7)
number of compressor functioning hours above which a maintenance request is signalled
0 = no function
DEFROSTING
if d8 = 0, 1 or 2, defrosting interval (8)
0 = defrosting at intervals will never be activated
if d8 = 3, maximum defrosting interval
type of defrosting
0 = ELECTRIC - during defrosting the compressor will remain off and the defrosting output will be activated; the evaporator fan activity will depend on parameter F2
1 = WITH HOT GAS - during defrosting the compressor will be switched-on and the defrosting output will be activated; the evaporator fan activity will depend on parameter

F2

2 = DUE TO COMPRESSOR STOPPING - during defrosting the compressor will remain off and the defrosting output will be deactivated; the evaporator fan activity will depend

on parameter F2

temperature of defrosting end (only if P3 = 1); see also d3
if P3 = 0 or 2, duration of defrosting
if P3 = 1, maximum duration of defrosting; see also d2
0 = defrosting will never be activated
defrosting on instrument switch-on (only if d8 = 0, 1, 2 or 3) (3)
1 = YES
if d4 = 0, minimum time between switch-on of the instrument and the activation of defrosting; see also i5 (3)
if d4 = 1, defrosting activation delay from instrument switch-on; see also i5 (3)
temperature displayed during defrosting
0 = cabinet temperature
1 = if, on activation of defrosting, the cabinet temperature is below “work set-point + r0”, at maximum “work set-point + r0”; if, on activation of defrosting, the cabinet

temperature is above “work set-point + r0”, at maximum the temperature of the cabinet on activation of defrosting (9)

during dripping (during dripping the compressor will remain off and the defrosting output will remain deactivated. If d16 = 0, the evaporator fan activity will depend on
parameter F2; if d16 ≠ 0, the evaporator fan will remain off)
defrosting activation method
0 = AT INTERVALS - defrosting will be activated when the instrument has remained on completely for time d0
1 = AT INTERVALS - defrosting will be activated when the compressor has been left on completely for time d0
2 = AT INTERVALS - defrosting will be activated when the evaporator temperature as remained below temperature d9 completely for time d0 (10)
3 = ADAPTIVE - defrosting will be activated when one of the following conditions occurs; see also d0: (10)

- condition 1: the evaporator temperature will be below temperature d22 and the compressor will have remained on totally for time d18
- condition 2: the evaporator temperature will drop below temperature d19

4 = IN REAL TIME - defrosting will be activated at the times set using parameters HD1.... Hd6
temperature of the evaporator over which the defrosting interval count is suspended (only if d8 = 2)
enabling of the defrosting alarm concluded due to maximum duration (“dFd” code; only if P3 = 1 and without evaporator probe error (“Pr2” code))
1 = YES
minimum duration of the compressor switch-on on activation of defrosting so that this can be activated (only if d1 = 1) (11)
duration of pre-dripping (during pre-dripping the compressor will remain off, the defrosting output will be activated and the evaporator fan will remain off)
number of evaporator temperature values used to calculate the relative average (for the activation of defrosting; only if d8 = 3); see also r7, i11 and i12
defrosting interval (only if d8 = 3 and for condition 1)
0 = defrosting due to condition 1 will never be activated
temperature of the evaporator below which defrosting is activated (relative to the average temperatures of the evaporator, i.e. “average of the evaporator temperatures +
d19) (only if d8 = 3 and due to condition 2); see also d17