EVCO EV6223P7 User Manual
Page 2
EVCO S.p.A.
This document belongs to Evco; unless you are authorized by Evco, you can not publish it.
Via Mezzaterra 6, 32036 Sedico Belluno ITALY
Evco does not take any responsibility about features, technical data and possible mistakes related in this document or coming by its use.
Phone +39-0437-852468 • Fax +39-0437-83648
Evco does not take any responsibility about damages coming by the non-observance of the additional information.
[email protected] • www.evco.it
Evco reserves the right to make any change without prior notice and at any time without prejudice the basic safety and operating features.
PT • 47/07
8
WORKING SETPOINTS AND CONFIGURATION PARAMETERS
8.1 Working setpoints
MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
r1
r2
°C/°F (1) 0.0
working setpoint
8.2 Configuration parameters
PARAM. MIN.
MAX.
U.M.
DEF.
WORKING SETPOINTS
SP
r1
r2
°C/°F (1) 0.0
working setpoint
PARAM. MIN.
MAX.
U.M.
DEF.
MEASURE INPUTS
CA1
-25.0
25.0
°C/°F (1) 0.0
cabinet probe offset
CA2
-25.0
25.0
°C/°F (1) 0.0
evaporator probe offset
P0
0
1
- - -
0
kind of probe
0 = PTC
1 = NTC
P1
0
1
- - -
1
decimal point Celsius degree (for the quantity to show during the normal operation)
1 = YES
P2
0
1
- - -
0
unit of measure temperature (2)
0 = °C
1 = °F
P3
0
2
- - -
1
evaporator probe function
0 = probe not enabled
1 = defrost probe and thermostat probe for the evaporator fan
2 = thermostat probe for the evaporator fan
P5
0
3
- - -
0
quantity to show during the normal operation
0 = cabinet temperature
1 = working setpoint
2 = evaporator temperature
3 = “cabinet temperature - evaporator temperature”
PARAM. MIN.
MAX.
U.M.
DEF.
MAIN REGULATOR
r0
0.1
15.0
°C/°F (1) 2.0
working setpoint differential
r1
-99.0
r2
°C/°F (1) -50.0
minimum working setpoint
r2
r1
99.0
°C/°F (1) 50.0
maximum working setpoint
r3
0
1
- - -
0
locking the working setpoint modification (with the procedure related in paragraph 3.1)
1 = YES
r4
0.0
99.0
°C/°F (1) 0.0
temperature increase during function Energy Saving; also look at i5
PARAM. MIN.
MAX.
U.M.
DEF.
COMPRESSOR PROTECTIONS
C0
0
240
min
0
compressor delay since you turn on the instrument
C1
0
240
min
5
minimum time between two activations in succession of the compressor; also compressor delay since
the end of the cabinet probe error (3)
C2
0
240
min
3
minimum time the compressor remains turned off
C3
0
240
s
0
minimum time the compressor remains turned on
C4
0
240
min
10
time the compressor remains turned off during the cabinet probe error; also look at C5
C5
0
240
min
10
time the compressor remains turned on during the cabinet probe error; also look at C4
PARAM. MIN.
MAX.
U.M.
DEF.
DEFROST
d0
0
99
h
8
defrost interval; also look at d8 (4)
0 = the defrost at intervals will never be activated
d1
0
1
- - -
0
kind of defrost
0 = electric defrost
1 = hot gas defrost
d2
-99.0
99.0
°C/°F (1) 2.0
defrost cutoff temperature (only if P3 = 1)
d3
0
99
min
30
defrost duration if P3 = 0 or 2; defrost maximum duration if P3 = 1
0 = the defrost will never be activated
d4
0
1
- - -
0
defrost when you turn on the instrument
1 = YES
d5
0
99
min
0
defrost delay when you turn on the instrument (only if d4 = 1); also look at i5
d6
0
1
- - -
1
temperature shown during the defrost
0 = cabinet temperature
1 = if to the defrost activation the cabinet temperature is below “working setpoint + r0”, at most “work-
ing setpoint + r0”; if to the defrost activation the cabinet temperature is above “working setpoint +
r0”, at most the cabinet temperature to the defrost activation (5)
d7
0
15
min
2
dripping duration
d8
0
2
- - -
0
kind of defrost interval
0 = the defrost will be activated when the instrument will have remained turned on the time d0
1 = the defrost will be activated when the compressor will have remained turned on the time d0
2 = the defrost will be activated when the evaporator temperature will have remained below the tem-
perature d9 the time d0 (6)
d9
-99.0
99.0
°C/°F (1) 0.0
evaporator temperature above which the count of the defrost interval is suspended (only if d8 = 2)
dA
0
99
min
0
minimum time the compressor must be remained turned on (to the defrost activation) in order that the
defrost can be activated (only if d1 = 1) (7)
PARAM. MIN.
MAX.
U.M.
DEF.
TEMPERATURE ALARMS
A0
0
1
- - -
0
temperature joined to the lower temperature alarm
0 = cabinet temperature
1 = evaporator temperature (8)
A1
-99.0
99.0
°C/°F (1) -10.0
temperature below which the lower temperature alarm is activated; also look at A0 and A2 (9)
A2
0
2
- - -
1
kind of lower temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working setpoint - A1”; consider A1 without sign)
2 = absolute (or A1)
A4
-99.0
99.0
°C/°F (1) 10.0
temperature above which the upper temperature alarm is activated; also look at A5 (9)
A5
0
2
- - -
1
kind of upper temperature alarm
0 = alarm not enabled
1 = relative to the working setpoint (or "working setpoint + A4”; consider A4 without sign)
2 = absolute (or A4)
A6
0
240
min
120
upper temperature alarm delay since you turn on the instrument
A7
0
240
min
15
temperature alarm delay
A8
0
240
min
15
upper temperature alarm delay since the end of the after dripping evaporator fan delay (10)
A9
0
240
min
15
upper temperature alarm delay since the deactivation of the door switch input (11)
PARAM. MIN.
MAX.
U.M.
DEF.
EVAPORATOR FAN
F0
0
4
- - -
1
evaporator fan activity during the normal operation
0 = turned off
1 = turned on
2 = according to the compressor
3 = according to F1 (12)
4 = turned off if the compressor is turned off, according to F1 if the compressor is turned on (12)
F1
-99.0
99.0
°C/°F (1) -1.0
evaporator temperature above which the evaporator fan is turned off (only if F0 = 3 or 4) (9)
F2
0
2
- - -
0
evaporator fan activity during the defrost and the dripping
0 = turned off
1 = turned on
2 = according to F0
F3
0
15
min
2
duration of the after dripping evaporator fan delay
PARAM. MIN.
MAX. U.M.
DEF.
DIGITAL INPUTS
i0
0
3
- - -
2
kind of digital input
0 = MULTIPURPOSE INPUT - in this case look at parameters i1, i5, i7, i8 and i9
1 = RESERVED
2 = DOOR SWITCH INPUT - in this case look at parameters i1, i2 and i3; the activation of the input will
turn off the evaporator fan (at most the time i3 or as long as the input will be deactivated)
3 = DOOR SWITCH INPUT - in this case look at parameters i1, i2 and i3; the activation of the input will
turn off the compressor and the evaporator fan (at most the time i3 or as long as the input will be
deactivated) (13)
i1
0
2
- - -
0
kind of contact digital input
0 = NO (the input will be active if you close the contact)
1 = NC (the input will be active if you open the contact)
2 = input not enabled
i2
-1
120
min
30
delay to signal the door switch input alarm
-1 = no signal
i3
-1
120
min
15
maximum duration of the effect provoked by the activation of the door switch input
-1 = the effect will last as long as the input will be deactivated
i5
0
6
- - -
3
effect provoked by the activation of the multipurpose input
0 = no effect
1 = SYNCHRONIZING THE DEFROSTS - spent the time d5 the defrost will be activated (14)
2 = ACTIVATING THE ENERGY SAVING - function Energy Saving will be activated (as long as the input
will be deactivated); also look at r4 (14)
3 = ACTIVATING THE EXTERNAL ALARM - spent the time i7 the display will show the code “iA” flashing
and the buzzer will be activated (as long as the input will be deactivated)
4 = ACTIVATING THE MANOSTAT - the compressor will be turned off, the display will show the code “iA”
flashing and the buzzer will be activated (as long as the input will be deactivated); also look at i7, i8
and i9
5 = TURNING OFF THE INSTRUMENT - the instrument will be turned off via software (as long as the
input will be deactivated); also look at C0, d4 and A6
6 = ACTIVATION COOLING - the compressor will be turned on (as long as the input will be deactivated);
in this case parameters C4 and C5 are not meaningful (14)
i7
0
120
min
0
if i5 = 3, delay to signal the multipurpose input alarm
if i5 = 4, compressor delay since the deactivation of the multipurpose input (15)
i8
0
15
- - -
0
number of multipurpose input alarms such as to provoke the instrument locked alarm (only if i5 = 4)
0 = alarm not enabled
i9
1
999
min
240
time without multipurpose input alarms in order that the alarm counter is cleared (only if i5 = 4)
PARAM. MIN.
MAX. U.M.
DEF.
SERIAL NETWORK (MODBUS)
LA
1
247
- - -
247
instrument address
Lb
0
3
- - -
2
baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
LP
0
2
- - -
2
parity
0 = none
1 = odd
2 = even
PARAM. MIN.
MAX. U.M.
DEF.
RESERVED
E9
0
1
- - -
1
reserved
(1)
the unit of measure depends on parameter P2
(2)
set the parameters related to the regulators appropriately after the modification of the parameter P2
(3)
if parameter C1 has value 0, the delay since the end of the cabinet probe error will however be 2 min
(4)
the instrument stores the count of the defrost interval every 30 min; the modification of parameter d0 has effect since the end of the previous
defrost interval or since the activation of a defrost by hand
(5)
the display restores the normal operation as soon as the after dripping evaporator fan delay ends and the cabinet temperature falls below
the one that has locked the display (or if a temperature alarm arises)
(6)
if parameter P3 has value 0 or 2, the instrument will work as if parameter d8 had value 0
(7)
if (to the defrost activation) the duration of the activation of the compressor is shorter than the time you have set with parameter dA, the
compressor will further remain turned on the fraction of time required to complete it
(8)
if parameter P3 has value 0, the instrument will work as if parameter A0 had value 0
(9)
the differential of the parameter is 2.0 °C/4 °F
(10)
during the defrost, the dripping and the evaporator fan delay the temperature alarms are not enabled, on condition that they have arisen
after the activation of the defrost
(11)
during the activation of the door switch input the upper temperature alarm is not enabled, on condition that it has arisen after the activation
of the input
(12)
if parameter P3 has value 0, the instrument will work as if parameter F0 had value 2
(13)
the compressor is turned off spent 10 s since the activation of the input; if the input is activated during the defrost or the after dripping
evaporator fan delay, the activation will provoke no effect on the compressor
(14)
the effect is not signalled
(15)
make sure the time you have set with parameter i7 is shorter than the one you have set with parameter i9.