beautypg.com

EVCO EPD4DF3 User Manual

Page 2

background image

EVCO S.p.A. | Code 104EPDE113 | Page 1 of 2 | PT 34/12

This document is exclusive property of EVCO; reproduction and disclosure are prohibited without express authorisation from EVCO.

EVCO is not liable for any features, technical data and possible errors stated in this document or deriving from use of the same.

EVCO cannot be considered liable for damages caused by failure to comply with warnings given in this document.

EVCO reserves the right to make any changes without forewarning, without jeopardising the basic safety and operating features.

EVCO S.p.A.
Via Feltre 81, 32036 Sedico (BL) ITALY
phone +39 0437 852468 | fax +39 0437 83648
email [email protected] | web www.evco.it

The device ensure a reinforced isolation among each ter-
minal of the high voltage contact and the remaining parts
of the device.
Displays:
-

128 x 64 pixel single colour (black with rearlighting
through white LEDs) LCD graphic display (not avail-
able in models EPD4BX3, EPD4BC3 and EPD4BF3)

-

signalling LEDs.

Digital outputs: 1 SPST 5 res. A @ 250 VAC (5 res. A @
30 VDC) output (electromechanical relay) which can be
set via configuration parameter as alarm output/solenoid
valve/resynchronization valve.
Electromechanical relay
Maximum switching power: 1,250 VA (150 W).
Mechanical life:

> to 5,000,000 operations.

Electrical life:

> to 100,000 operations.

Protection:

none.

The device ensure a reinforced isolation among each ter-
minal of the digital output and the remaining parts of the
device.
Bipolar stepper motor output: 4 wires bipolar stepper
motor output.
Bipolar stepper motor output
Input voltage:

21 VDC ±10%.

Output voltage:

27... 36 VDC (18... 24 VDC if
supplied by the backup mod-
ule).

Maximum output current: 1 A.
Driver type:

chopper (or constant current).

Protection:

none.

Type of actions and additional features: 1C.
Communication ports:
3 ports
-

1 non optoisolated CAN port, with CANBUS communi-
cation protocol (not available in model EPD4BX3)

-

1 non optoisolated RS-485 port, with MODBUS com-
munication protocol (not available in models EPD4BX3
and EPD4BC3)

-

1 non optoisolated programming port, with MODBUS
communication protocol.

Power supply remote user interface: 22... 35 VDC, 100 mA
max.

This manual is related to the following products: