beautypg.com

EVCO EVXS214N9 User Manual

Page 4

background image

EVCO S.p.A. • Code 104XS214E104 • page 4/8

PT • 27/12

• if parameter F0 is set at 3 or 4, the instrument will function

as if parameter is set at 2

• the alarm output will be activated (only if parameter u1

is set at 3)

Pr3

Condenser probe error
Solutions:
• the same as the previous case but relative to the condenser

probe

Main consequences:
• the overheated condenser alarm (“COH” code) will

never be activated

• the compressor blocked due to condenser temperature

alarm (“CSd” code) will never be activated

• the alarm output will be activated (only if parameter u1

is set at 3)

• if parameter u1 is set at 6, the condenser fan will function

in parallel to the compressor

rtc

Clock error
Solutions:
• set the day and real time again
Main consequences:
• if parameter d8 is set at 4, the instrument will function as

if parameter is set at 0

• the HACCP function will not supply information relative

to the date and time the alarm occurred

• the Energy Saving function will not be available in real

time

• the alarm output will be activated (only if parameter u1

is set at 3)

ErC

Error of compatibility user interface-control module
Solutions:
• check the compatibility user interface-control module

(check the data related in the labels)

Main consequences:
• the control module will keep working correctly

ErL

Error of communication user interface-control module
Solutions:
• check the connection user interface-control module
Main consequences:
• the control module will keep working correctly

When the cause of the alarm disappears, the instrument restores normal
functioning, except for the clock error (“rtc” code) that requires setting
of the day and real time.
11

TECHNICAL DATA

11.1

Technical data

User interface container: open frame board.
Control module container: open frame board.
User interface protection rating (front): IP 00.
Control module protection rating: IP 00.
User interface connections: extractable screw terminal block (at
the control module).
The user interface connects to the control module via a 4-way cable:
the maximum length allowed for the connection cable is 20 m
(65.614 ft; the cable is not supplied with the instrument).
Control module connections: 6.3 mm faston (0.248 in, power
supply and outputs), screw terminal board (to the user interface and
inputs), 6-pole connector (serial port).
Temperature of use: from 0 to 55 °C (from 32 to 131 °F, 10 ... 90%
relative humidity without condensate).
User interface power supply: the user interface is powered by the
control module.
Control module power supply: 115 ... 230 VCA, 50/60 Hz, 10 VA.
Maintaining the clock data in a power cut: 24 h with battery
charged.
Battery charging time: 2 min without interruptions (the battery is
charged by the instrument power supply).
Alarm buzzer: incorporated (in the user interface).
Measurement inputs: 3 (cabinet probe, evaporator probe and
condenser probe) for NTC probes
Digital inputs: 2 (door micro switch and multipurpose) for normally
open/normally closed contact (potential free contact, 5 V 1 mA).
Range of measurement: from -40 to 105 °C (from 40 to 220 °F).
Resolution: 0.1 °C/1 °C/1 °F.
Digital outputs: 4 relays:

• compressor relay: 30 A res. @ 250 VCA (NO

contact)

• defrosting relay: 16 A res. @ 250 VCA (contact

in exchange)

• evaporator fan relay: 8 A res. @ 250 VCA (NO

contact)

• fourth output relay: 16 A res. @ 250 VCA (NO

contact).

The maximum current allowed on the loads is 20 A.
Serial port: port for communication with the Parameters Manager
set-up software system or to the monitoring and supervision system of
RICS plants (via TTL, with MODBUS communication protocol) or with
the EVKEY programming key.