Evco S.p.A. • Code 104K214E04 • page 4/6

10

OPERATIONAL SETPOINT AND CONFIGURATION PARAMETERSE

10.1 Operational setpoint

MIN.

MAX. U.O.M.

DEF.

r1

r2

°C/°F (1) 0,0

10.2 Configuration paramaters
PARAM. MIN.

MAX. U.O.M.

DEF.

SP

r1

r2

°C/°F (1) 0,0

PARAM. MIN.

MAX. U.O.M.

DEF.

CA1

-25,0 25,0

°C/°F (1) 0,0

CA2

-25,0 25,0

°C/°F (1) 0,0

CA3

-25,0 25,0

°C/°F (1) 0,0

P0

0

1

- - - -

1

P1

0

1

- - - -

1

P2

0

1

- - - -

0

P3

0

2

- - - -

1

P4

0

3

- - - -

3

P5

0

4

- - - -

0

P6

0

4

- - - -

0

PARAM. MIN.

MAX. U.O.M.

DEF.

r0

0,1

15,0

°C/°F (1) 2,0

r1

-99,0 r2

°C/°F (1) -50,0

r2

r1

99,0

°C/°F (1) 50,0

r3

0

1

- - - -

0

r4

0,0

99,0

°C/°F (1) 0,0

PARAM. MIN.

MAX. U.O.M.

DEF.

C0

0

240

min

0

C1

0

240

min

5

C2

0

240

min

3

C3

0

240

s

0

C4

0

240

min

10

C5

0

240

min

10

C6

0,0

200,0 °C/°F (1) 80,0

C7

0,0

200,0 °C/°F (1) 90,0

C8

0

15

min

1

C9

0

120

s

5

C10

0

9999 h

1000

PARAM. MIN.

MAX. U.O.M.

DEF.

d0

0

99

h

8

d1

0

1

- - - -

0

d2

-99,0 99,0

°C/°F (1) 2,0

d3

0

99

min

30

d4

0

1

- - - -

0

d5

0

99

min

0

d6

0

1

- - - -

1

d7

0

15

min

2

d8

0

3

- - - -

0

d9

-99,0 99,0

°C/°F (1) 0,0

dA

0

99

min

0

PARAM. MIN.

MAX. U.O.M.

DEF.

A0

0

2

- - - -

0

A1

-99,0 99,0

°C/°F (1) -10,0

OPERATIONAL SETPOINT
operational setpoint

OPERATIONAL SETPOINT
operational setpoint
INGRESSI DI MISURA
cabinet probe offset
evaporator probe offset
auxiliary probe offset (only if P4 = 1 or 2)
probe type
0 = PTC
1 = NTC
degree Celsius decimal point (for the quantity displayed during normal operation)
1 = YES
unit of temperature measurement (2)
0 = °C
1 = °F
evaporator probe function
0 = no probe
1 = defrosting probe and evaporator fan thermostat probe
2 = evaporator fan thermostat probe
fourth input function
0 = no probe
1 = sensor input (auxiliary probe, display probe)
2 = sensor input (auxiliary probe, condenser probe)
3 = digital input (multifunction input)
quantity displayed during normal operation
0 = cabinet temperature
1 = operational setpoint
2 = evaporator temperature
3 = "cabinet temperature - evaporator temperature"
4 = temperature detected by the auxiliary probe (only if P4 = 1 or 2)
quantity displayed by the remote indicator
0 = cabinet temperature
1 = operational setpoint
2 = evaporator temperature
3 = "cabinet temperature - evaporator temperature"
4 = temperature detected by the auxiliary probe (only if P4 = 1 or 2)
MAIN CONTROLLER
operational setpoint differential
minimum operational setpoint
maximum operational setpoint
block operational setpoint change (with the procedure indicated in paragraph 3.2)
1 = YES
temperature increase during Energy Saving function (only if P4 = 3 and i5 = 2 or 3); refer also to HE1 and HE2
COMPRESSOR PROTECTIONS (3)
compressor delay from device power on (4)
minimum time between two successive compressor operations; also compressor delay on resolution of cabinet probe error (5) (6)
minimum compressor shut-down time (5)
minimum compressor start-up time
duration of compressor shut-down during cabinet probe error; see also C5
duration of compressor start-up during cabinet probe error; see also C4
condenser temperature above which the condenser overheating alarm is activated (only if P4 = 2) (7)
condenser temperature above which the compressor block alarm is activated (only if P4 = 2)
compressor block alarm delay (only if P4 = 2) (8)
compressor 2 delay from power up of compressor 1 (only if u1 = 3)
number of hours of compressor operation above which maintenance request is indicated
0 = no function
DEFROSTING
defrost interval (only if d8 = 0, 1 or 2) (9)
0 = regular periodic defrosting will never be activated
type of defrosting
0 = electric
1= hot gas
defrost end temperature (only if P3 = 1)
defrost duration if P3 = 0 or 2; maximum defrost duration if P3 = 1
0 = defrosting will never be activated
defrosting at device power on (only if d8 = 1, 2 or 3) (4)
1 = YES
defrost delay from device power on (only if d4 = 1); see also i5 (4)
temperature displayed during defrosting (only if P5 = 0)
0 = cabinet temperature
1 = if, on activation of defrosting the cabinet temperature is below the "operational setpoint + r0", at most "operational setpoint + r0"; if on activation of defrosting the cabinet

temperature is above the "operational setpoint + r0", at most the cabinet temperature at activation of defrosting (10)

drip-drain duration
method of activation of defrosting
0 = PERIODIC - defrosting will be activated when the device has been left running for the length of time d0
1 = PERIODIC - defrosting will be activated when the compressor has been running for the length of time d0
2 = PERIODIC - defrosting will be activated when the evaporator temperature remains below the temperature set by d9 for the amount of time et by d0 (11)
3 = REAL TIME - defrosting will be activated at the times established by parameters Hd1 ... Hd6
the evaporator temperature above which the defrost interval count is suspended (only if d8 = 2)
minimum compressor on duration on activation of defrosting so that they may be activated (only if d1 = 1) (12)
TEMPERATURE ALARMS
temperature associated with the minimum temperature alarm
0 = cabinet temperature
1 = evaporator temperature (13)
2 = temperature detected by the auxiliary probe (only if P4 = 1 or 2) (14)
the temperature below which the minimum temperature alarm is activated; see also A0 and A2 (7)