beautypg.com

Carrier EVERGREEN 19XR User Manual

Page 5

background image

5

Start Carrier Network Manager

1. Minimize the expandable keyboard.
2. Select (tap) the Windows Start icon in the lower left cor-

ner of the screen.

3. Select “All Programs.”
4. Select “ComfortVIEW.”
5. Select “Carrier Network Manager” (Fig. 8).

Configure ComfortVIEW™ Software on Touch
Screen —

For ease of use, a default CCN database called

“Local Chillers” was created and set up for communications

through COM 1 port of the display. An example of the display

showing the default CCN databases and the Local Chiller data-

base is shown in Fig. 9.

The other CCN databases listed in Fig. 9 are provided as

templates of chiller versions. Each CCN database contains one

chiller database in Network Manager and associated workspac-

es in Workspace Manager. These files are provided to allow the

cloning of these workspaces for your specific chiller.

More CCN databases are planned for release to support older

software versions and future software releases.

If at any time, Carrier Network Manager issues the operator

message, “Your Access Level will not allow you to perform

this function” or if there is a problem during the configuration

procedure, it may be necessary to log out of ComfortVIEW

and log in again.

To login, use the local administrative account and password.

The username is “sa” and the password is “carrier”, both in

lowercase (Fig. 10). The username and password are entered

using the expandable keyboard. The keyboard can be displayed

by tapping the small keypad icon.

It will be necessary to upload your specific chiller into the

Local Chiller CCN database to be able to communicate with

your chiller.

1. Double tap on “Local Chillers.”
2. Double tap on “”Local Chillers - My chiller.”
3. Carrier Network Manager is started with “Local Chillers -

My chiller” is displayed, as shown in Fig. 11.

4. Select the “

+

” icon at the top of the “Local Chillers - My

chiller” screen.

5. “CCN Element Definition” screen is displayed. Enter

“Element name” (for this example we are using “My

19XR”) and “Element description” using onscreen key-

board, then press “OK” (Fig. 12). Enter “Bus” and “Ele-

ment” numbers.

NOTE: Default numbers are 0 for Bus and 1 for Element.

Fig. 8 — Start Carrier Network Manager

a19-1899

Fig. 9 — Default and Local Chillers Database

a19-1900

Fig. 10 — Login Prompt

a19-1901

Fig. 11 — “Local Chillers - My chiller” Screen

a19-1902