beautypg.com

Carrier AQUAZONE 50VS User Manual

Page 8

background image

8

Step 2 — Check Unit —

Upon receipt of shipment at

the jobsite, carefully check the shipment against the bill of

lading. Make sure all units have been received. Inspect the car-

ton or crating of each unit, and inspect each unit for damage.

Ensure the shipping company makes proper notation of any

shortages or damage on all copies of the freight bill. Concealed

damage not discovered during unloading must be reported to

the shipping company within 15 days of receipt of shipment.
NOTE: It is the responsibility of the purchaser to file all

necessary claims with the shipping company.

1. Be sure that the location chosen for unit installation pro-

vides ambient temperatures maintained above freezing.

Well water applications are especially susceptible to

freezing.

2. Be sure the installation location is isolated from sleeping

areas, private offices and other acoustically sensitive

spaces.
NOTE: A sound control accessory package may be used

to help eliminate sound in sensitive spaces.

3. Check local codes to be sure a secondary drain pan is not

required under the unit.

4. Be sure unit is mounted at a height sufficient to provide

an adequate slope of the condensate lines. If an appropri-

ate slope cannot be achieved, a field-supplied condensate

pump may be required.

5. Provide sufficient space for duct connection. Do not

allow the weight of the ductwork to rest on the unit.

6. Provide adequate clearance for filter replacement and

drain pan cleaning. Do not allow piping, conduit, etc. to

block filter access.

7. Provide sufficient access to allow maintenance and

servicing of the fan and fan motor, compressor and coils.

Removal of the entire unit from the closet should not be

necessary.

8. Provide an unobstructed path to the unit within the closet

or mechanical room. Space should be sufficient to allow

removal of unit if necessary.

9. Provide ready access to water valves and fittings, and

screwdriver access to unit side panels, discharge collar,

and all electrical connections.

10. Where access to side panels is limited, pre-removal of the

control box side mounting screws may be necessary for

future servicing.

STORAGE — If the equipment is not needed immediately at

the jobsite, it should be left in its shipping carton and stored in a

clean, dry area of the building or in a warehouse. Units must be

stored in an upright position at all times. If carton stacking is

necessary, stack units a maximum of 3 cartons high. Do not re-

move any equipment from its shipping package until it is need-

ed for installation.
PROTECTION — Once the units are properly positioned on

the jobsite, cover them with either a shipping carton, vinyl film,

or an equivalent protective covering. Cap open ends of pipes

stored on the jobsite. This precaution is especially important in

areas where painting, plastering, or spraying of fireproof mate-

rial, etc. is not yet complete. Foreign material that accumulates

within the units can prevent proper start-up and necessitate

costly clean-up operations.

Before installing any of the system components, be sure to

examine each pipe, fitting, and valve, and remove any dirt or

foreign material found in or on these components.

INSPECT UNIT — To prepare the unit for installation, com-

plete the procedures listed below:

1. Compare the electrical data on the unit nameplate with

ordering and shipping information to verify that the

correct unit has been shipped.

2. Do not remove the packaging until the unit is ready for

installation.

3. Verify that the unit’s refrigerant tubing is free of kinks or

dents, and that it does not touch other unit components.

4. Inspect all electrical connections. Be sure connections are

clean and tight at their terminations.

5. Remove any blower support cardboard from inlet of the

blower.

6. Locate and verify any accessory kit located in compressor

and/or blower section.

7. Remove any access panel screws that may be difficult to

remove once unit is installed.

Step 3 — Locate Unit —

The following guidelines

should be considered when choosing a location for a WSHP:
• Units are for indoor use only.
• Locate in areas where ambient temperatures are between

39 F and 102 F and relative humidity is no greater than

75%.

• Provide sufficient space for water, electrical and duct

connections.

• Locate unit in an area that allows easy access and removal

of filter and access panels.

• Allow enough space for service personnel to perform

maintenance.

• Return air must be able to freely enter the space if unit needs

to be installed in a confined area such as a closet.

Step 4 — Install Drywall —

All rough-in instructions

and drawings are designed for a single layer of

5

/

8

in. thick dry-

wall. Refer to Fig. 6. Rough-in dimensions will be affected if

drywall thickness is different than

5

/

8

in., the return panel will

not fit snugly to the wall and form a tight seal. Install drywall

using conventional construction methods. Drywall cannot be

fastened to the studs with adhesive alone; a mechanical fasten-

er such as drywall screws must be used.

Vacuum all drywall dust and construction debris from coils,

drain pans and blower discharge plenum after cutting out sup-

ply and return holes for grilles. When installation is complete,

cover cabinet supply and return air openings.

Do not allow paint or wall texture over-spray to contact coil,

fan or other unit components. Warranties are void if paint or

other foreign debris is allowed to contaminate internal unit

components.

Step 5 — Install Cabinet and Riser

SYSTEM PIPING ARRANGEMENTS — Figure 7 shows

some of the common piping layouts for water source heat

pumps. 2-pipe systems are depicted but the same methods can

be applied to 4-pipe systems.

CAUTION

DO NOT store or install units in corrosive environments or

in locations subject to temperature or humidity extremes

(e.g., attics, garages, rooftops, etc.). Corrosive conditions

and high temperature or humidity can significantly reduce

performance, reliability, and service life. Always move

units in an upright position. Tilting units on their sides may

cause equipment damage.