Step 12 — Install Supply Grille

Refer to Fig. 2, 3, and 12 to determine grille size and location

based on the type and size of the unit cabinet/chassis combina-

tion. Perform the following to install supply grilles over the

cabinet discharge openings.

1. To prevent supply air from short circuiting back into the

return air panel a supply duct extension(s) is provided

with each cabinet.

2. Insert the grille into the cabinet supply duct extension(s).

Assure that the grille flange rests against the drywall cov-

ering the cabinet.

3. Secure the grille to the drywall with the screws provided.

PRE-START-UP

Check the following before system start-up.

1. Balancing/shutoff valves: Ensure that all isolation valves

are open and water control valves are wired.

2. Line voltage and wiring: Verify that voltage is within an

acceptable range for the unit and wiring and fuses/break-

ers are properly sized. Verify that low voltage wiring is

complete.

3. Entering water and air: Ensure that entering water and

air temperatures are within operating limits of Table 9.

SC

SG

SL

SA

SE

SB

SF

SK

SJ

SUPPLY

DRAIN

RETURN

RISERS

CABINET

RIGHT

LEFT

FRONT

DB

DF

DK

DC

DG

DA

DE

DJ

DL

NA

NC

NB

NO SUPPLY OPENINGS

SINGLE SUPPLY

TA

TJ

TE

TRIPLE SUPPLY

DOUBLE SUPPLY

SUPPLY AIR TO ROOM

RETURN AIR FROM ROOM

Dimension to suit local codes

and installer

R

C

S

MASTER

SLAVE

Field-supplied and installed piping

Cross hoses in slave cabinet

(36 in. hoses required in slave unit)

R

C

S

R

S

LEGEND

C — Condensate Drain
R — Return
S — Supply

a50-8302.eps

Fig. 12 — 50VS Unit Airflow Arrangements

NOTES:

1. Refer to the table and the airflow arrangements above to determine grille

size and location based on the type and size of the unit cabinet/chassis
combination.

2. The riser compartment is defined as being the rear of each unit. Supply air

grilles and return air/access panel can be any side except rear.

3. Return air location also denotes the control location and servicing access.
4. Single discharge openings are not recommended for 50VSI-VSN units.

Triple discharge openings are not recommended for 50VSA-VSD units.

Supply Grille Sizes and Arrangements

UNIT

DISCHARGE (in.)

Single Double

Triple

50VSA,B

(Small Cabinet)

14x12

10x8

10x8

50VSC,D

(Small Cabinet)

14x12

10x8

10x8

50VSE,F

(Small Cabinet)

14x12

10x8

10x8

50VSG,H

(Small Cabinet)

14x12

10x8

10x8

50VSI,J

(Large Cabinet)

16x14

12x10

12x10

50VSK,L

(Large Cabinet)

16x14

12x10

12x10

50VSM,N

(Large Cabinet)

16x14

12x10

12x10