Fig. 10 — typical 50vs unit control wiring – Carrier AQUAZONE 50VS User Manual

Page 14

background image

14

BLOWER SPEED WIRING

Unit

Orange

Brown

Black

Blue

Red

50VSA,B

Low

High

50VSC,D

Low

High

50VSE,F

Low

High

50VSG,H

Low

High

50VSI,J

Low

High

50VSK,L

Low

High

50VSM,N

Low

High

a50-8352

NOTES:

1. Used for optional communicating thermostat.
2. Cut JP1 or JP2 for dry contact output accessory relay 1 and 2.
3. If a single stage thermostat is used, place a jumper wire between

Y1 and Y2 at P1 terminal.

4. If the disconnect option is not installed, connect the power to the

L1 and L2 lugs on the compressor contactor.

5. Accessory relays 24-vac maximum, activated by compressor

output.

6. For 230-v operation, remove the red wire and replace with the

orange wire.

7. Before connecting BacNet™ or LonWorks® card, connect com-

municating thermostat, then short J1 (2-3). If adding terminating
resistance, short J1 (1-2).

BR1

Fan Relay Speed 1

BR2

Fan Relay Speed 2

CC

Compressor Contactor

CO

Condensate Overflow

CR

Compressor Relay

DAT

Discharge Air Temperature

FP1

Freeze Protection Water Side

FP2

Freeze Protection Air Side

HP

High Pressure Switch

LP

Low Pressure Switch

LWT — Leaving Water Temperature
RV

Reversing Valve

Factory Low Voltage Wiring
Factory High Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Optional Block
Internal PCB Connection

Quick Connect Terminal

Screw Terminal

Relay Coil

Capacitor

High Pressure Switch

Low Pressure Switch

Temperature Thermistor

Condensate Switch

Relay Contacts

LEGEND

Fig. 10 — Typical 50VS Unit Control Wiring