Conventional systems, Heat pump systems – Braeburn 1200NC User Manual

Page 5

background image

4

NOTES - Conventional Systems

[1] If batteries are installed the 24 Volt AC common connection is optional
[2] Remove factory installed jumper for dual transformer systems
[3] In dual transformer systems, transformer common must come from

cooling transformer

[4] If needed for system

Provide disconnect and overload protection as required.

2 HEAT / 1 COOL Single Transformer (1200NC Only)

Set System Type to NORM

R 24 Volt AC Power
W1 Heat Relay Stage 1
W2 Heat Relay Stage 2
Y1 Compressor Relay Stage 1
G Fan Relay
C 24 Volt AC Transformer Common [note 1]

Conventional Systems

(cont.)

Typical Wiring Configurations

NOTE: The “Installer Switch” option will be configured in the next step.

Heat Pump Systems

1 HEAT / 1 COOL - No Auxiliary Heat

Set Installer Switch to HP

Rh*

24 Volt AC Power

Rc*

Connected to Rh with supplied Jumper Wire

O or B Changeover Valve [note 2]
Y1

Compressor Relay (appears as

Y1 on 1200NC)

G

Fan Relay

C

24 Volt AC Transformer Common

[note 1]

2 HEAT / 1 COOL - Including Auxiliary Heat (1200NC only)

Set Installer Switch to HP

R

24 Volt AC Power

O or B Changeover Valve [note 2]
Y1

Compressor Relay (1st stage heating/cooling)

W2

Auxiliary Heat Relay (2nd stage heating)

[note 3]

W1/E Emergency Heat Relay [note 3]
G

Fan Relay

C

24 Volt AC Transformer Common

[note1]

(Continued)

*Appears as R on 1200NC (single transformer)