4 installer settings – Braeburn 5220 Installer Guide User Manual
Page 10

INSTRUCTIONS
DAY/TIME
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer
Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped. These
settings are indicated below with comments. More detail on each setting follows this table.
Installer Guide 10
1. Press and hold down the
RETURN
and
buttons for 3 seconds.
2. Release both buttons and the first installer
setting will be displayed.
3. Change settings as required using the
or portion of the SpeedBar
®
.
4. Press
NEXT
(HOLD)
or
BACK
(PROG)
to
move to the next or previous setting,
press
RETURN
to exit.
No. Installer Setting
Factory
Setting
Comments
(
Notes follow this table)
Default
Options
(More information follows this table)
1 Residential or
RES
RES
Select for Residential profile
or Commercial Profile
COMM
Select for Commercial profile
2 Programming Mode
7 PROG
7 PROG
Select for 7 day programming mode
[note 1]
52 PROG
Select for 5-2 day programming mode
NO PROG
Select for non-programmable mode
3 Clock Format
12 HR
12 HR
Select for 12 hour clock
24 HR
Select for 24 hour clock
4 Temperature Scale
F DEG
F DEG
Select for Fahrenheit display
C DEG
Select for Celsius display
5 Auto Changeover
oF AUTO
oF AUTO
Disables Auto Changeover mode
ON AUTO
Enables Auto Changeover mode
11CONV
Select for 1H/1C Conventional system
22CONV
Select for 2H/2C Conventional system
6 System Type
11CONV
11HP
Select for 1H/1C Heat Pump system
22HP
Select for 2H/2C Heat Pump system
32HP
Select for 3H/2C Heat Pump system
1HD
Select for Heat Only Hydronic system
11HD
Select for Hydronic Heat/1C system
7 1st Stage Differential
0.5 DIF1
0.5, 1.0 or
Select a 1st stage temperature differential of .5°,
2.0 DIF1
1° or 2° F (.25°, .5° or 2° C)
8 2nd Stage Differential
2.0 DIF2
1.0, 2.0, 3.0, Select a 2nd stage temperature differential of 1°,
[note 2]
4.0, 5.0 or 2°, 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3° C)
6.0 DIF2
9 3rd Stage Differential
2.0 DIF3
1.0, 2.0, 3.0, Select a 3rd stage temperature differential of 1°, 2°,
[note 2]
4.0, 5.0 or 3°, 4°, 5° or 6° F (.5°, 1°, 1.5°, 2°, 2.5° or 3°C)
6.0 DIF3
4 Installer Settings
NOTE: Shaded areas below do not apply to the 5020.
INSTRUCTIONS
DAY/TIME
BACK
NEXT