2100_10_11.pdf, Troubleshooting – Braeburn 2100 User Manual
Page 6
![background image](/manuals/661689/6/background.png)
10
11
TROUBLESHOOTING
6
TROUBLESHOOTING
6
cont.
SYMPTOM
POTENTIAL SOLUTION
SYMPTOM
POTENTIAL SOLUTION
Verify your program setpoint time entries. The heating and
cooling programs utilize the same setpoint times, but have
individual setpoint temperatures for the
MORN, DAY, EVE and
NIGHT setpoints. See Setting Your Energy Saving Program
section of this manual.
Thermostat program has been temporarily overridden and
program indicator is flashing in the display. Wait till next setpoint
and the temporary override will expire or change setpoint
temperature to desired comfort level.
Thermostat program is in Extended Hold (Vacation) Mode and
HOLD and TEMP is showing in display. Press HOLD or RETURN
button to release permanent hold and return the thermostat to
normal program operation.
Thermostat turns
heating or cooling
system on too often
or not often enough.
Increase or decrease first stage temperature differential setting
as appropriate to provide the desired performance level. See
Setting Temperature Differential section of this manual.
Thermostat turns on
second (auxiliary)
stage of heating too
quickly or not quickly
enough.
Increase or decrease second (auxiliary) stage temperature
differential setting as appropriate to provide the desired
performance level. See Setting Temperature Differential section
of this manual.
Thermostat will not
follow program
setpoints.
Check current time of day, day of week program settings. Make
sure to verify
AM/PM indicator is accurately displaying desired
time settings. See Setting Current Time of Day and Day of Week
section of this manual.
Check to see if
OFF is shown in display. This indicates that the
system is turned off at the thermostat. Move the system selector
switch to the
HEAT or COOL position. After the compressor short
cycle protection 5-minute period expires the system should start
within several seconds.
Low battery indicator
is shown in
thermostat display.
Replace back-up batteries as soon as possible.
See Low Battery Detection and Replacement section of
this manual.
OFF is shown in
thermostat display
and heating or
cooling system will
not start.
This indicates that the system is turned off at the thermostat.
Move the system selector switch to the
HEAT or COOL position.
After the compressor short cycle protection 5-minute period
expires the system should start within several seconds.
Thermostat display
is blank.
It is possible that AC power is not present at the thermostat and
the back-up batteries are fully discharged. Check fuse, circuit
breaker and thermostat wiring as appropriate to verify AC power
is available. Replace back-up batteries before re-programming
thermostat to make sure you have back-up power. See Low
Battery Detection and Replacement and Setting Your Energy
Saving Program sections of this manual.
If AC Power is present, call a professional service technician to
verify thermostat and system performance.
Thermostat will not
allow me to program
a setpoint
temperature higher
than 90˚ F (32˚ C).
This is above the normal thermostat temperature setting range
of 45˚ to 90˚ F (7˚ to 32˚ C).
Thermostat will not
allow me to program
a set point
temperature lower
than 45˚ F (7˚ C).
This is below the normal thermostat temperature setting range
of 45˚ to 90˚ F (7˚ to 32˚ C).
LO is shown in the
thermostat display
where the room
temperature is
normally displayed.
HI is shown in the
thermostat display
where the room
temperature is
normally displayed.
The temperature sensed by the thermostat is higher than the
99˚ F (37˚ C) upper limit of the thermostats display range. The
display will return to normal after the sensed temperature
lowers within the 40˚ to 99˚ F (5˚ to 37˚ C) display range. Turn on
the cooling system or use other methods to lower the
temperature accordingly.
This condition could occur from the system being turned off
during an exceptionally warm period or upon installation when
the thermostat has been stored for a long period of time in a
warm vehicle or location prior to being installed. The thermostat
is equipped with a mechanical high temperature safety switch
that will turn off the thermostat should the temperature exceed
99˚ F (37˚ C) in the heat mode.
The temperature sensed by the thermostat is lower than
the 40˚ F (5˚ C) lower limit of the thermostats display range.
The display will return to normal after the sensed temperature
rises within the 40˚ to 99˚ F (5˚ to 37˚ C) display range. If the
temperature in the controlled space seems to be normal, wait
for the thermostat to acclimate to the correct room temperature.
If the room seems to be colder than usual, turn on the heating
system to raise the temperature as needed for comfort within
the room.
This condition could occur from the system being turned off
during a cold weather period or upon installation when the
thermostat has been stored for a long period of time in a cold
vehicle or location prior to being installed. The thermostat should
be allowed to warm up prior to installation to allow proper
heating control once installed.
Wiring Diagram for 2 Stage Heat, 1 Stage Cool