2100_2_3.pdf, 23 installation, Testing your new thermostat – Braeburn 2100 User Manual

Page 2: Installation

background image

2

3

INSTALLATION

2

2.1

Replacing Existing Thermostat

cont.

4. After labeling and removing all wires from terminals, unscrew the existing thermostat

sub-base from wall. Make sure to secure wires to prevent them from slipping back

into the hole in the wall.

NOTE:

This thermostat is designed for use with a 24 Volt AC low voltage multi-

stage gas, oil or electric heating or cooling systems. Do not use this thermostat on

applications with voltages above 30 Volts AC.

2.2

Installing Your New Thermostat

NOTE:

If you are installing this thermostat in a new installation be sure to locate

the thermostat 4 to 5 feet above the floor in accordance with applicable building

codes. Make sure to install the thermostat in a location that provides good airflow

characteristics and avoid areas behind doors, near corners, air vents, direct sunlight

or near any heat generating device. Installation in any of these areas could impact

thermostat performance.

1. Always turn off power to the air conditioning or heating system prior to installing your

new thermostat.
2. Place system switch on front of thermostat to the OFF position.
3. Place fan control switch on front of thermostat to the AUTO position.
4. Remove front of thermostat body from sub-base by pressing release latch on bottom

of front body.
5. Place the thermostat sub-base against wall in the desired thermostat location.
6. Guide thermostat wires through center hole in sub-base. Continue to hold sub-base

against wall.
7. Mark placement of mounting holes as appropriate and drill using a 3/16" drill bit.
8. Gently tap supplied plastic anchors into the holes in the wall.
9. Place the thermostat sub-base against the wall in the desired location, making sure

the mounting holes are aligned as appropriate and the thermostat wires are properly

inserting through opening in middle of sub-base.
10. Fasten the sub-base to wall using supplied screws.
11. Connect wires to quick wiring terminal block as appropriate using the new terminal

designations. Refer to Wiring Diagram section of this manual if required for assistance.
12. Make sure all of the wire connections are secure and are not touching any other

terminal to prevent electrical shorts and potential damage to the thermostat.
13. Turn the front thermostat body over exposing the rear view of the circuit board.
14. Locate the internal ˚F / ˚C switch on the circuit board.
15. Using your finger, gently flip the switch toward the preferred temperature ˚F / ˚C scale.
16. Locate the internal fan option switch, HG (Gas) / HE (Elec) on the circuit board. This

switch controls the heating system fan delay. Select gas for gas or oil fired systems.

This will allow the furnace to run for a few seconds before initiating the fan. Select

electric for systems with electric furnace elements that require the fan to come

on immediately.
17. Using your finger, gently flip the switch towards the HG (Gas) or HE (Elec) selection

which indicates the low voltage heating system the thermostat will control.
18. Attach front body of thermostat to sub-base of thermostat being careful to align the

terminal pins on the front body with the terminal block on the sub-base.
19. Open front thermostat door and open battery compartment door.

TESTING YOUR

NEW THERMOSTAT

3

NOTE:

Test your thermostat prior to programming any user settings. Pressing the

RESET button will erase any user entries for time of day, day of week, option settings

and programming if previously programmed. This will return all user settings and

return them to their default values. Remember, this will erase all programs entered by

the user.

WARNING!

Read BEFORE Testing

• Do not short (or jumper) across terminals on the gas valve or at the heating or

cooling system control board to test the thermostat installation. This could damage

the thermostat and void the warranty.

• Do not select COOL mode of operation if the outside temperature is below

50˚ F (10˚ C). This could possibly damage the controlled cooling system and may

cause personal injury.

• This thermostat includes an automatic compressor protection feature to avoid

potential damage to the cooling system from short cycling. This thermostat

automatically provides a 5-minute delay after turning off the cooling system output

to protect the compressor.

cont.

NOTE:

If you installed the batteries prior to accomplishing steps 14 and 15, then you

will need to reset the thermostat to register your thermostat switch configurations prior to

programming. Gently press the RESET button on the front of the thermostat using a paper

clip or a small pencil tip.

1. Place the system switch in the HEAT position.
2. Press the button on the keypad until the setpoint temperature setting is a minimum

of 3 degrees higher than the current room temperature. The heating system should

start within several seconds. The fan may not turn on immediately due to the heating

system built-in fan delay.
3. Place the system switch in the OFF position. The heating system should stop within

several seconds.
4. Place the system switch in the COOL position.
5. Press the button on the keypad until the setpoint temperature is a minimum of 3

degrees lower than the current room temperature.
6. The cooling system should start within several seconds. Place the system switch in

the

OFF position.

7. Place the fan switch in the ON position. The system blower should start.
8. Place the fan switch in the AUTO position. The system blower should stop.

INSTALLATION

2

cont.

20. Install two new "AA" alkaline batteries into battery compartment. Make sure to

locate the positive (+) ends of the batteries and match them with the positive (+)

terminals located in the battery compartment.
21. Close battery compartment.
22. Restore system power so you can test installation.