Control panel operating procedures – AERCO BMK 3.0 LN Dual Fuel June 2010 User Manual
Page 28
CONTROL PANEL OPERATING PROCEDURES
Table 3-3. Setup Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Passsword
0 9999 0
Language English
English
Time
12:00 am
11:59 pm
Date 01/01/00
12/31/99
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
Comm Address
0
127
0
Baud Rate
2400, 4800, 9600, 19.2K
9600
Software
Ver 0.00
Ver 9.99
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
NOTE
The Configuration Menu settings shown in
Table 3-4 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Boiler, BMK Boiler LN,
BMK Boiler Dual, KC Water
Heater, KC Water Heater LN,
Water Heater 2010
BMK Boiler
Dual
Unit Size
0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
3.0 MBTU, 3.5 MBTU
4.0 MBTU, 5.0 MBTU
6.0 MBTU
3.0 MBTU
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
3-6