3 natural gas combustion calibration, Initial start-up – AERCO BMK 2.0 LN Nat. Gas User Manual

Page 32

background image

INITIAL START-UP


Figure 4.1

1/8” Gas Plug Location

4.2.3 PREPARING THE FLUE VENT
PROBE HOLE

1. Locate and remove the plug on the left or

right side of the exhaust manifold (see
Figure 4.2).

2. Adjust the stop on the combustion analyzer

probe, if so equipped, so that it extends
approximately midway into the flue gas flow.
Do not insert the probe at this time.

Figure 4.2

A

Location

nalyzer Probe Hole

4.2.4 INSTALLING THE DIFFERENTIAL
REGULATOR ADJUSTMENT TOOL FOR
NATURAL GAS UNIT.

1. Remove the cap from the differential

pressure regulator (see Figure 4.3).

2. Place the gasket from the regulator cap onto

the regulator adjustment tool.

3. Prior to installing the tool on the regulator,

pull up the screwdriver blade of the tool.
Then thread the tool into the regulator and
hand tighten.

4. Engage the tool’s screwdriver blade into the

regulator’s adjustment screw slot.

CAP GASKET

REGULATOR CAP

REGULATOR

ADJUSTMENT
TOOL (P.N. 123643)

DIFFERENTIAL

PRESSURE

REGULATOR

Figure 4.3

Differential Regulator Adjustment Tool

Installation For Natural Gas Unit

4.3 NATURAL GAS COMBUSTION
CALIBRATION

The Benchmark ships combustion calibrated
from the factory. Recalibration as part of a start-
up is necessary due to altitude, gas BTU
content, gas supply piping and supply gas
pressure. Factory test data sheets are shipped
with each unit as a reference.

4-2