The transmission distances listed below are farthest ones recommended for each giving
wire d iameter when the 24 VAC v oltage loss ratio is below 10%(for equipment powered by
AC, the allowed maximum voltage loss ratio is 10%).For example, 5 sets of indoor equipment
with n ominal power as 12 VA and 2sets outdoor equipment with nominal power as 50 VA,
install 28 feet (8m) away from transformer, need total power of 160VA(5
12VA 2
50VA),
need a wire with a minimum diameter of 1.0mm.
9. 4 24VAC Wire Diameter and Transmission Distance
Comparison chart
Wire Diameter
(mm)
P o w e r ( v a )
38
Appendix