beautypg.com

Beckett CG4 User Manual

Page 7

background image

7

CG4 Burner Manual

Section: INSPECT/PREPARE INSTALLATION SITE

5. Any leakage between tiles, around clean-out doors,

or around the vent pipe should be sealed.

6. A Draft regulator is required, it shall be a double-

acting type, agency recognized for use with gas

vent systems.

7. The design and sizing of the appliance’s vent

system shall comply with the requirements of NFPA

54 Chapters 12 and 13.

8. A chimney flue shall extend at least 3 feet above

the highest point at which the chimney comes in

contact with the roof, and not less than 2 feet above

the highest roof surface or structure within 10 feet

horizontally of the chimney. Refer to

Figure 4.

Some local codes and gas

utilities require the installation of

a thermal Safety switch on the double-acting draft

control, or draft hood. This is a very good practice

and provides the following protection:

The thermal safety switch senses flue gas spillage

caused by blocked flue exhaust, prolonged down-draft,

or insufficient draft. The safety is wired in series with the

burner control circuit and shuts the burner off, when the

spillage of hot flue gases is detected.

Minimum Clearence: 2 FT.

Figure 4 – Chimney Design - Above the Roof

NOTE: Correct chimney design is shown by dotted lines. Incorrect chimney design, as shown by the solid

lines, may result in down-drafts.

Insulated stainless steel chimney liners

The new designs of furnaces and boilers in conjunction

with flame retention gas burners are more efficient.

One result of increased efficiency is lower flue gas

temperatures. As flue gases rise in the chimney, they

cool and condense when they reach the dew point.

The condensation mixes with sulphur in the flue gases

creating sulfuric acid. The acid attacks the chimney

mortar, brick and clay liners causing corrosion,

deterioration and blockage of the chimney. Eventually

the blockage could prevent exhausting the flue gases.

Instead, the flue gases vent out the barometric damper

into the living space.

Therefore it is strongly recommended that an approved

insulated stainless steel chimney liner be installed. The

installing contractor is solely responsible for installation

of the proper vent system.

○ For those installations not requiring a chimney, such

as through-the-wall vented appliances, follow the

instructions given by the appliance and power venter

(if used) manufacturers.